Drive Parameter Registers (U1-XX / Monitor Only)
REGISTER
PARAMETER
PARAMETER
PARAMETER
BIT
LIMITS / DESCRIPTION
(in hex)
FUNCTION
SETTING
NO.
020h
U1-01
Frequency Reference
Frequency Reference of drive (0.1 Hz) (1)
021h
U1-02
Output Frequency
Output Frequency of drive (0.1 Hz) (1)
022h
U1-03
Output Current
Drive rating / 8192
023h
U1-04
Control Method
0
V/f Control
1
V/f with PG Feedback
2
Open Loop Vector
3
Flux Vector
024h
U1-05
Motor Speed
Motor Speed (in 0.1 Hz)
025h
U1-06
Output Voltage
Output Voltage (in 0.1 V)
026h
U1-07
DC Bus Voltage
DC Bus Voltage (in 1 V)
027h
U1-08
Output Power
Output Power (in 0.1 kW)
028h
U1-09
Torque Reference
Torque Reference (in 0.1%)
029h
U1-10
Input Terminal Status
0
Input Terminal 1 closed
1
Input Terminal 2 closed
2
Input Terminal 3 closed
3
Input Terminal 4 closed
4
Input Terminal 5 closed
5
Input Terminal 6 closed
6
Input Terminal 7 closed
7
Input Terminal 8 closed
02Ah
U1-11
Output Terminal Status
0
Control Circuit terminals 9 & 10: ìClosedî
1
Control Circuit terminals 25 & 27: ìClosedî
2
Control Circuit terminals 26 & 27: ìClosedî
3-6
not used
7
Control Circuit terminals 18 & 20: ìClosedî
Notes (for this page only):
1. Scaling depends on setting of o1-03.