The Message Format 6-9
Write Multiple Registers - 10h
The multiple register write function (10h) allows the master to write data to the driveís registers.
The multiple register write message format is shown below.
Command Message
Each GPD 515ís slave address is set in advance by the drive parameter H5-01. Valid slave
addresses must be in the range of 1 to 31 decimal (1 to 1F hex). No two slaves may have the
same address. The master addresses the slave by placing the slave address in the address field
of the message. In the command message above, the slave is addressed at 1.
By setting the slave address to zero (0) in the address section of the message, the master can
send operation signals (register 1h) and frequency reference (register 2h) to all slaves on the
network. The master can send a single transmission to all the slaves simultaneously. This is
called simultaneous broadcasting. In a simultaneous broadcast message all of the slaves on the
network act upon one message. Simultaneous Broadcast registers are shown in Chapter 7,
Registers (page 7-2).
The function code of this message is 10h (write multiple registers).
The starting register number is the first register to be written to. In the command message above
the starting number is 01h, indicating that the first register is the frequency reference. A listing of
the GPD 515ís registers is shown in Chapter 7, Registers.
01h
SLAVE ADDRESS
FUNCTION CODE
10h
00h
01h
START-
ING
REGISTER
NO.
UPPER
LOWER
04h
CRC-16
NO. OF DATA BYTES
QTY.
00h
02h
UPPER
LOWER
00h
01h
UPPER
LOWER
DATA TO
NEXT
REGISTER
17h
70h
UPPER
LOWER
DATA TO
FIRST
REGISTER
6Dh
B7h
LOWER
UPPER
The first register, 01h
(Operation Command) has
a value of 01h or 1 dec.
(forward run command)
The next register, 02h
(Frequency Reference) has
a value of 1770h or 6000
dec. (60.00 Hz)
Summary of Contents for GPD 515/G5 Modbus RTU
Page 1: ...GPD 515 G5 Modbus RTU Technical Manual ...
Page 24: ...6 4 The Message Format ...
Page 30: ...6 10 The Message Format ...