Digital Operation Display Functions and Levels
5
-
7
C1-01
Acceleration
time 1
Sets the acceleration time to accelerate
from 0 Hz to the maximum output fre-
quency.
0.0 to
6000.0
10.0 s
Yes
Q
200H
C1-02
Deceleration
time 1
Sets the deceleration time to decelerate
from the maximum output frequency to
0 Hz.
Yes
Q
201H
d2-01
Frequency refer-
ence upper limit
Sets the frequency reference upper limit
as a percentage of the max. output fre-
quency.
0.0 to
110.0
100.0%
No
A
289H
d2-02
Frequency refer-
ence lower limit
Sets the frequency reference lower limit
as a percentage of the maximum output
frequency.
0.0 to
110.0
0.0%
No
A
28AH
E1-01
Input voltage
setting
Sets the inverter input voltage. This set
value will be the basis for the protection
functions.
155 to
255
*2
200 V
*2
No
Q
300H
E2-01
Motor rated cur-
rent
Sets the motor rated current in Amps.
This set value becomes the base value for
motor protection and torque limit. It is an
input data for autotuning.
0.32 to
6.40
*5
1.90 A
*4
No
Q
30EH
F6-01
Operation selec-
tion after com-
munications
error
Set the stopping method for communica-
tions errors.
0: Deceleration to stop using the
deceleration time in C1-02
1: Coast to stop
2: Emergency stop using the deceleration
time in C1-09
3: Continue operation
0 to 3
1
No
A
3A2H
H3-02
Gain (terminal
A1)
Sets the frequency as a percentage of the-
maximum output frequency, when 10 V is
input.
0.0 to
1000.0
100.0%
Yes
A
411H
H3-03
Bias (terminal
A1)
Sets the frequency as a percentage of the
maximum frequency, when 0 V is inut.
-100.0
to
+100.0
0.0%
Yes
A
412H
H3-10
Gain (terminal
A2)
Sets the input level when terminal A2
input is 10 V (20 mA) according to the
100% value of the function set in constant
H3-09.
0.0 to
1000.0
100.0%
Yes
A
419H
H3-11
Bias (terminal
A2)
Sets the input level when terminal A2 is
0 V (4 mA/0 mA) according to the 100%
value of the function set in constant
H3-09.
-100.0
to
+100.0
0.0%
Yes
A
41AH
L2-01
Momentary
power loss
detection
0: Disabled (DC bus undervoltage (UV1)
detection)
1: Enabled (Restarted when the power
returns within the time set in L2-02.
When L2-02 is exceeded, DC bus
undervoltage is detected.)
2: Enabled while CPU is operating.
(Restarts when power returns during
control operations. Does not detect DC
bus undervoltage.)
0 to 2
0
No
A
485H
L2-02
Momentary
power loss ride-
thru time
Ridethrough time, when Momentary
Power Loss Selection (L2-01) is set to 1,
in units of seconds.
0 to 2.0
0.1 s
*1
No
A
486H
Con-
stant
Number
Name
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Access
Level
MEMO-
BUS
Regis-
ter