5
-36
Torque Detection: L6
Con-
stant
Number
Name
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Access
Level
MEMO-
BUS
Register
Page
L6-01
Torque detection
selection
0: Overtorque/undertorque
detection disabled.
1: Overtorque detection only with
speed agreement; operation
continues (warning is output).
2: Overtorque detected
continuously during operation;
operation continues (warning is
output).
3: Overtorque detection only with
speed agreement; output stopped
upon detection.
4: Overtorque detected
continuously during operation;
output stopped upon detection.
5: Undertorque detection only with
speed agreement; operation
continues (warning is output).
6: Undertorque detected
continuously during operation;
operation continues (warning is
output).
7: Undertorque detection only with
speed agreement; output stopped
upon detection.
8: Undertorque detected
continuously during operation;
output stopped upon detection.
0 to 8
6
No
A
4A1H
6-31
L6-02
Torque detection
level
Inverter rated current is set as
100%.
0 to 300
15%
No
A
4A2H
6-31
L6-03
Torque detection
time
Sets the overtorque/undertorque
detection time.
0.0 to
10.0
10.0 s
No
A
4A3H
6-31