5
-28
Analog Inputs: H3
2
f
ref
/f
out
agree 1 (detection width L4-02 is used.)
6-27
3
f
ref
/f
set
agree 1 (ON: Output frequency = ±L4-01, with detection width L4-02 used and during
frequency agree)
6-27
4
Frequency detection 1 (ON: +L4-01
≥
output frequency
≥
-L4-01, with detection width L4-02
used)
6-27
5
Frequency detection 2 (ON: Output frequency
≥
+L4-01 or output frequency
≤
-L4-01, with
detection width L4-02 used)
6-27
6
Inverter operation ready
READY: After initialization or no faults
6-64
7
During DC bus undervoltage (UV) detection
6-64
8
During baseblock (NO contact, ON: during baseblock)
6-64
9
Frequency reference source selection (ON: Frequency reference from Operator)
6-64
A
Run command source selection status (ON: Run command from Operator)
6-64
B
Overtorque/undertorque detection 1 NO (NO contact, ON: Overtorque/undertorque detection)
6-31
C
Loss of frequency reference (Effective when 1 is set for L4-05)
6-44
E
Fault (ON: Digital Operator communications error or fault other than CPF00 and CPF01 has
occurred.)
6-64
F
Not used. (Set when the terminal is not used.)
-
10
Minor fault (ON: Alarm displayed)
6-64
11
Fault reset command active
6-65
12
Timer function output
6-82
17
Overtorque/undertorque detection 1 NC (NC Contact, OFF: Torque detection)
6-31
1A
Reverse direction
6-65
1E
Restart enabled (ON: Restart enabled)
6-45
1F
Motor overload (OL1, including OH3) pre-alarm (ON: 90% or more of the detection level)
6-33
20
OH pre-alarm (temperature reached L8-02)
6-65
38
Drive enabled
6-65
39
Drive waiting (start delay time b1-11 is active)
6-65
3A
During OH and reduced Frequency
6-65
3B
RUN command from option card/communications
6-65
Constant
Number
Name
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Access
Level
MEMO-
BUS
Register
Page
H3-02
Gain (terminal
A1)
Sets the frequency as a percentage
of themaximum output fre-
quency, when 10 V is input.
0.0 to
1000.0
100.0%
Yes
A
411H
6-22
H3-03
Bias (terminal
A1)
Sets the frequency as a percentage
of the maximum frequency, when
0 V is inut.
-100.0
to
+100.0
0.0%
Yes
A
412H
6-22
H3-08
Multi-function
analog input ter-
minal A2 signal
level selection
0: 0 to +10V (11 bit).
2: 4 to 20 mA (9-bit input).
3: 0 to 20 mA (9-bit input)
Switch current and voltage input
using the switch S1 on the control
terminal board.
0, 2, 3
2
No
A
417H
6-22
Setting
Value
Function
Page