Digital Operator Functions
6
-
103
Monitor Selection (o1-01)
Using constant o1-01 the third monitor item that is displayed in drive mode can be selected. This function has
no effect on the optional LCD-operator (JVOP-160).
Monitor Display when the Power Supply is Turned ON (o1-02)
Using constant o1-02 the monitor item (U1-
) that is to be displayed on the Digital Operator when the
power supply is turned ON can be selected.
Changing Frequency Reference and Display Units o1-03)
Set the Digital Operator frequency reference and display units using constant o1-03. The setting in o1-03 will
affect the display units of the following monitor items:
•
U1-01 (Frequency Reference)
•
U1-02 (Output Frequency)
•
U1-05 (Motor Speed)
•
U1-20 (Output Frequency after Soft Start)
•
d1-01 to d1-04 (Frequency references)
Disabling the LOCAL/REMOTE Key (o2-01)
Set o2-01 to 0 to disable the LOCAL/REMOTE Key on the Digital Operator.
If the key is disabled, it cannot be used anymore to switch over the frequency reference source or the RUN
command source between LOCAL and REMOTE.
o2-08
Cumulative operation time selec-
tion
0: Cumulative time when the Inverter power is on. (All
time while the Inverter power is on is accumulated.)
1: Cumulative Inverter run time. (Only Inverter output
time is accumulated.)
0 or 1
0
No
A
o2-09
Initialize Mode
2: Europe
5: PV-E Spec
2 or 5
2
No
A
o2-10
Fan operation time setting
Set the initial value of the fan operation time using hour
units.
The operation time accumulates from the set value.
0 to
65535
0
No
A
o2-12
Fault trace initialize
0: Disable
1: Initialize (= zero clear) after setting ”1“ o2-12 will be
returned to ”0“
0 or 1
0
No
A
o2-14
Energy monitor initialize
Resets the monitor parameter U1-29 and U1-30 back to
zero.
0: No change
1: Reset to zero
0 or 1
0
No
A
o2-15
HAND key function selection
If set to 0 the HAND button on the digital operator is dis-
abled and the drive will not enter the HAND mode and
start to run when the HAND button is pressed.
0: HAND button disabled
1: HAND button enabled
0 or 1
1
No
A
Con-
stant
Number
Name
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Access
Level
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com