Wiring Control Circuit Terminals
2
-
25
Control Circuit Wiring Precautions
Observe the following precautions when wiring control circuits.
•
Separate control circuit wiring from main circuit wiring (terminals R/L1, S/L2, T/L3, U/T1, V/T2, W/T3,
,
1,
2, and
3) and other high-power lines.
•
Separate wiring for control circuit terminals MA, MB, MC, M1, M2, M3, and M4 (contact outputs) from
wiring to other control circuit terminals.
•
If using an optional external power supply, it shall be a UL Listed Class 2 power supply source.
•
Use twisted-pair or shielded twisted-pair cables for control circuits to prevent operating faults.
•
Ground the cable shields so as to maximise the contact area of the shield and ground.
•
Cable shields have to be grounded on both cable ends.
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com