T: Motor Autotuning
* 1. The factory setting depends on the Inverter capacity. (The value for a 200 V Class Inverter for 0.4 kW is given.)
* 2. The setting range is from 10% to 200% of the Inverter rated output current. (The value for a 200 V Class Inverter for 0.4 kW is given.)
U: Monitor Constants
Status Monitor Constants: U1
* The unit is set in o1-03 (frequency units of reference setting and monitor).
Con-
stant
Number
Name
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Access
Level
MEMO-
BUS
Register
Page
T1-02
Motor output
power
Sets the output power of the motor
in kilowatts.
0.00 to
650.00
0.40
kW
*1
No
A
702H
4-7
T1-04
Motor rated cur-
rent
Sets the rated current of the motor
in Amps.
0.32 to
6.40
*2
1.90 A
*1
No
A
704H
4-7
Con-
stant
Number
Name
Description
Output Signal Level Dur-
ing Multi-Function Analog
Output
Min.
Unit
MEMO-
BUS
Register
U1-01
Frequency refer-
ence
Monitors/sets the frequency refer-
ence value.*
10 V: Max. frequency
(0 to + 10 V possible)
0.01
Hz
40H
U1-02 Output frequency Monitors the output frequency.*
10 V: Max. frequency
(0 to + 10 V possible)
0.01
Hz
41H
U1-03 Output current
Monitors the output current.
10 V: Inverter rated output
current
(0 to +10 V, absolute value
output)
0.1 A
42H
U1-06 Output voltage
Monitors the output voltage refer-
ence value.
10 V: 200 VAC (400 VAC)
(0 to +10 V output)
0.1 V
45H
U1-07 DC bus voltage
Monitors the main DC bus volt-
age.
10 V: 400 VDC (800 VDC)
(0 to +10 V output)
1 V
46H
U1-08 Output power
Monitors the output power (inter-
nally detected value).
10 V: Inverter capacity
(max. applicable motor
capacity)
(0 to + 10 V possible)
0.1
kW
47H