-48
Factory Settings that Change with the Inverter Capacity (o2-04)
200 V Class Inverters
Note: Attach a Momentary Power Interruption Compensation Unit if compensation for power interruptions of up to 2.0 seconds is required for 200 V class
Inverters with outputs of 0.4 to 11 kW.
* If C6-02 is set to 0, 1, or F and the initial value of C6-03 and C6-04 is 2.0 kHz, the initial settings for C6-02 are as follows: 2: 5.0 kHz, 3: 8.0 kHz, 4: 10
kHz, 5: 12.5 kHz, and 6: 15 kHz. If the carrier frequency is set higher than the factory setting for Inverters with outputs of 30 kW or more, the Inverter
rated current will need to be reduced.
Note: Attach a Momentary Power Interruption Compensation Unit if compensation for power interruptions of up to 2.0 seconds is required for 200 V class
Inverters with outputs of 0.4 to 11 kW.
* If C6-02 is set to 0, 1, or F and the initial value of C6-03 and C6-04 is 2.0 kHz, the initial settings for C6-02 are as follows: 2: 5.0 kHz, 3: 8.0 kHz, 4: 10
kHz, 5: 12.5 kHz, and 6: 15 kHz. If the carrier frequency is set higher than the factory setting for Inverters with outputs of 30 kW or more, the Inverter
rated current will need to be reduced.
Con-
stant
Number
Name
Unit
Factory Setting
–
Inverter Capacity
kW
0.4
0.75
1.5
2.2
3.7
5.5
7.5
11
15
o2-04
kVA selection
–
0
1
2
3
4
5
6
7
8
b8-04
Energy-saving coeffi-
cient
–
288.20
223.70
169.40
156.80
122.90
94.75
72.69
70.44
63.13
C6-02
Carrier frequency selec-
tion
*
–
6
6
6
6
6
6
6
6
6
E2-01
Motor rated current
A
1.90
3.30
6.20
8.50
14.00
19.60
26.60
39.7
53.0
E2-03
Motor no-load current
A
1.20
1.80
2.80
3.00
4.50
5.10
8.00
11.2
15.2
E2-05
Motor line-to-line resis-
tance
Ω
9.842
5.156
1.997
1.601
0.771
0.399
0.288
0.230
0.138
L2-02
Momentary power loss
ridethru time
s
0.1
0.1
0.2
0.3
0.5
1.0
1.0
1.0
2.0
L2-03
Min. baseblock (BB)
time
s
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
L2-04
Voltage recovery time
s
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
L8-02
Overheat pre-alarm level
°
C
95
95
95
95
95
95
95
95
95
Con-
stant
Number
Name
Unit
Factory Setting
–
Inverter Capacity
kW
18.5
22
30
37
45
55
75
90
110
o2-04
kVA selection
–
9
A
B
C
D
E
F
10
11
b8-04
Energy-saving coeffi-
cient
–
57.87
51.79
46.27
38.16
35.78
31.35
23.10
23.10
23.10
C6-02
Carrier frequency selec-
tion*
–
6
6
4
3
3
3
3
3
1
E2-01
Motor rated current
A
65.8
77.2
105.0
131.0
160.0
190.0
260.0
260.0
260.0
E2-03
Motor no-load current
A
15.7
18.5
21.9
38.2
44.0
45.6
72.0
72.0
72.0
E2-05
Motor line-to-line resis-
tance
Ω
0.101
0.079
0.064
0.039
0.030
0.022
0.023
0.023
0.023
L2-02
Momentary power loss
ridethru time
s
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
L2-03
Min. baseblock (BB)
time
s
1.0
1.0
1.1
1.1
1.2
1.2
1.3
1.5
1.7
L2-04
Voltage recovery time
s
0.6
0.6
0.6
0.6
0.6
1.0
1.0
1.0
1.0
L8-02
Overheat pre-alarm level
°
C
95
95
95
95
95
95
95
95
95