background image

PAGE 12

Aquavar IPC Start-Up Genie

CentriPro

• Minimum Run Time: Set the minimum time the motor must have been running 

before entering sleep mode.

• Minimum Sleep Time: Set the minimum time the motor must stay in sleep 

mode. 

• Flow Check Window: Flow check window is the amount of pressure increase 

used in the flow check function.

• Flow Check Low Time: Flow check low time defines how long the controller will 

run at the setpoint during the flow check function.

• Flow Check High Time: Flow check high time defines how long the controller 

will run at Flow Check  setpoint during the flow check function. 

• Run the No Flow Power Calibration Setup: Start of auto setup of power data for No-Flow Power tuning.

NO FLOW POWER CALIBRATION
A no flow condition can be detected 
by monitoring the power consumption 
of the pump. Typically a pump’s power 
consumption will drop when the pump is run 
at no flow. The graph shown below illustrates 
a typical pump power curve at the pump 
design flow and at no flow.

When the pump is operated at no flow, 
the power consumption will follow the 
no flow power curve for that specific 
pump. The controller monitors the power 
consumption of the pump. If the pump’s 
power consumption falls to the no flow 
power curve, a no flow condition can be 
detected by the controller. In order to detect 
a no flow condition for various pumps, the no 
flow power curve needs to be programmed 
into the drive. The No Flow Power Calibration 
Setup provides the method to program the 
no flow power curve into the controller.

22-33

Low Speed [Hz]

(50% of 4-14)

22-37

High Speed

[Hz]

(85% of 4-14)

4-14

Motor Speed

High Limit

[Hz]

Speed (Hz)

Power (HP)

22-35

Low

Speed

Power

[HP]

22-39

No

Water/
Loss of

Prime

Limit

22-39

Scaled

Design Flow Power

No Flow Power

CHAPTER 6: PUMP PROTECTION

 (continued)

Summary of Contents for CentriPro Aquavar

Page 1: ...AQUAVAR Intelligent Pump Controller START UP GENIE PROGRAMMING MANUAL PROGRAMMING MANUAL IM262R00...

Page 2: ...6 2 3 Duplex Control 7 2 4 Speed Control 8 2 5 Test Run Mode 8 Chapter 3 Feedback 9 Chapter 4 Setpoint 10 Chapter 5 Flow Compensation 10 Chapter 6 Pump Protection 11 Chapter 7 Digital Input 15 Chapter...

Page 3: ...cations Table 1 Setup Selection SETUP SELECTION 1 Motor 2 Application 3 Feedback Autoset 4 Setpoint 5 Flow Compensation 6 Pump Protection Setup 7 Digital Input 8 Relay and Analog Output Setup 9 Commun...

Page 4: ...tor nameplate data Motor Frequency Select the motor frequency from the motor nameplate data Motor Nominal Speed Enter the rated motor speed from the motor nameplate data Motor Current Enter the rated...

Page 5: ...ons APPLICATION TYPE Constant Pressure Pressure control using a pressure transducer or other external feedback device with analog signal Flow Control Flow control using a flow meter or other external...

Page 6: ...nalog signal CONTROL UNITS Select the appropriate control units for the application psi GPM ft etc RAMP TIME The Ramp Time is the time to transition from stop to full speed Fast 5s accelerate and 3s d...

Page 7: ...ncies too close together will cause frequent starts and stops of the lag pump LAG PUMP STOP FREQUENCY This parameter defines the speed to which system needs to drop before stopping the lag pump Settin...

Page 8: ...rrent set in par 6 10 6 12 TERMINAL 53 HIGH REFERENCE Enter the reference of feedback value that corresponds to the voltage or current set in par 6 11 6 13 MINIMUM SPEED REFERENCE Set the minimum spee...

Page 9: ...imum value programmed for that input AUTOSET For basic applications users are able to set motor information operation mode and Autoset the rest of the parameters With support for the most common contr...

Page 10: ...ive when DI 33 closed CHAPTER 5 FLOW COMPENSATION This setup allows configuration of up to 2 setpoints Flow Compensation Adjusts the setpoint based on speed flow to compensate for system head loss Is...

Page 11: ...llows the pump to stop when a no flow condition is detected A no flow condition means that the setpoint has been satisfied and the pump is running at the sleep frequency Minimum Sleep Frequency Enter...

Page 12: ...ion of the pump Typically a pump s power consumption will drop when the pump is run at no flow The graph shown below illustrates a typical pump power curve at the pump design flow and at no flow When...

Page 13: ...ng the affinity laws The No Flow Power Calibration Set up is now complete The power data can be saved by pressing OK and then the down arrow If any issues were encountered during the calibration proce...

Page 14: ...ll trigger the Under Pressure Function This value is set as a of Maximum Reference Feedback Under Pressure Difference Example Given Under Pressure Delay 10 seconds Under Pressure Difference 10 Setpoin...

Page 15: ...4 20mA 0 Torque Limit 4 16 Torque Limit Motor Mode 102 Feedback 200 200 to 200 of 20 14 Maximum Reference Feedb 0 20 mA 135 Torque 0 nom 4 20mA 0 Motor rated torque 103 Motor Current 0 Imax 0 Inverte...

Page 16: ...activate on Run Relay on Delay This is the delay time from when the relay function is triggered to when the relay transitions its state To modify the relay delay time first press OK and use the up an...

Page 17: ...the minimum delay time between receiving a request and transmitting a response This is used for overcoming modem turnaround delays Maximum Response Delay Specify the maximum permissible delay time be...

Page 18: ...asing this value optimizes polling for the token Control Timeout Time enter the maximum time expected to pass between the receptions of two consecutive telegrams If this time is exceeded it indicates...

Page 19: ...ther drive select Yes to copy setup to LCP then transfer LCP to another drive and select Copy from LCP in the Start Up Genie CHAPTER 11 COPY FROM LCP LOCAL CONTROL PANEL Allows all of the controlled p...

Page 20: ...tive solutions to meet our world s water needs Developing new technologies that will improve the way water is used conserved and re used in the future is central to our work We move treat analyze and...

Reviews: