background image

PAGE 11

Aquavar IPC Start-Up Genie

CentriPro

• At No Flow Speed: Set the pressure value corresponding to speed at no flow.

• Pressure at Rated Speed: Set the pressure value corresponding to pressure at 

rated speed. 

• Flow at Rated Speed: Set the flow value corresponding to flow at rated speed. 

• Flow at Design Point: Set the flow value corresponding to flow at design point

• Dual Pump Value Increase: Defines the increase in setpoint when a lag pump 

starts. This value is entered as a % of the Maximum Reference

CHAPTER 6: PUMP PROTECTION 

This setup configures Sleep Mode, Flow Check, No Water/Loss of Prime and Pump Protect functions.

• Sleep Mode: Sleep Mode allows the pump to stop when a no flow condition is 

detected. A no flow condition means that the setpoint has been satisfied and the 
pump is running at the sleep frequency.

• Minimum/Sleep Frequency: Enter the minimum limit for the motor speed. 

The motor speed low limit can be set to correspond with the minimum output 
frequency of the motor shaft. The Motor Speed Low Limit must not exceed the 
Motor Frequency.

• Sleep Delay: The sleep delay time is the time the pump must stay at the sleep 

frequency before going to sleep.

• Restart Difference 1: Set the difference between setpoint #1 and actual at 

which the system must exit sleep mode. Value is set as a % of setpoint #1.

• Restart Difference 2: Set the difference between setpoint #2 and actual at 

which the system must exit sleep mode. Value is set as a % of setpoint #2.

CHAPTER 5: FLOW COMPENSATION

 (continued)

Summary of Contents for CentriPro Aquavar

Page 1: ...AQUAVAR Intelligent Pump Controller START UP GENIE PROGRAMMING MANUAL PROGRAMMING MANUAL IM262R00...

Page 2: ...6 2 3 Duplex Control 7 2 4 Speed Control 8 2 5 Test Run Mode 8 Chapter 3 Feedback 9 Chapter 4 Setpoint 10 Chapter 5 Flow Compensation 10 Chapter 6 Pump Protection 11 Chapter 7 Digital Input 15 Chapter...

Page 3: ...cations Table 1 Setup Selection SETUP SELECTION 1 Motor 2 Application 3 Feedback Autoset 4 Setpoint 5 Flow Compensation 6 Pump Protection Setup 7 Digital Input 8 Relay and Analog Output Setup 9 Commun...

Page 4: ...tor nameplate data Motor Frequency Select the motor frequency from the motor nameplate data Motor Nominal Speed Enter the rated motor speed from the motor nameplate data Motor Current Enter the rated...

Page 5: ...ons APPLICATION TYPE Constant Pressure Pressure control using a pressure transducer or other external feedback device with analog signal Flow Control Flow control using a flow meter or other external...

Page 6: ...nalog signal CONTROL UNITS Select the appropriate control units for the application psi GPM ft etc RAMP TIME The Ramp Time is the time to transition from stop to full speed Fast 5s accelerate and 3s d...

Page 7: ...ncies too close together will cause frequent starts and stops of the lag pump LAG PUMP STOP FREQUENCY This parameter defines the speed to which system needs to drop before stopping the lag pump Settin...

Page 8: ...rrent set in par 6 10 6 12 TERMINAL 53 HIGH REFERENCE Enter the reference of feedback value that corresponds to the voltage or current set in par 6 11 6 13 MINIMUM SPEED REFERENCE Set the minimum spee...

Page 9: ...imum value programmed for that input AUTOSET For basic applications users are able to set motor information operation mode and Autoset the rest of the parameters With support for the most common contr...

Page 10: ...ive when DI 33 closed CHAPTER 5 FLOW COMPENSATION This setup allows configuration of up to 2 setpoints Flow Compensation Adjusts the setpoint based on speed flow to compensate for system head loss Is...

Page 11: ...llows the pump to stop when a no flow condition is detected A no flow condition means that the setpoint has been satisfied and the pump is running at the sleep frequency Minimum Sleep Frequency Enter...

Page 12: ...ion of the pump Typically a pump s power consumption will drop when the pump is run at no flow The graph shown below illustrates a typical pump power curve at the pump design flow and at no flow When...

Page 13: ...ng the affinity laws The No Flow Power Calibration Set up is now complete The power data can be saved by pressing OK and then the down arrow If any issues were encountered during the calibration proce...

Page 14: ...ll trigger the Under Pressure Function This value is set as a of Maximum Reference Feedback Under Pressure Difference Example Given Under Pressure Delay 10 seconds Under Pressure Difference 10 Setpoin...

Page 15: ...4 20mA 0 Torque Limit 4 16 Torque Limit Motor Mode 102 Feedback 200 200 to 200 of 20 14 Maximum Reference Feedb 0 20 mA 135 Torque 0 nom 4 20mA 0 Motor rated torque 103 Motor Current 0 Imax 0 Inverte...

Page 16: ...activate on Run Relay on Delay This is the delay time from when the relay function is triggered to when the relay transitions its state To modify the relay delay time first press OK and use the up an...

Page 17: ...the minimum delay time between receiving a request and transmitting a response This is used for overcoming modem turnaround delays Maximum Response Delay Specify the maximum permissible delay time be...

Page 18: ...asing this value optimizes polling for the token Control Timeout Time enter the maximum time expected to pass between the receptions of two consecutive telegrams If this time is exceeded it indicates...

Page 19: ...ther drive select Yes to copy setup to LCP then transfer LCP to another drive and select Copy from LCP in the Start Up Genie CHAPTER 11 COPY FROM LCP LOCAL CONTROL PANEL Allows all of the controlled p...

Page 20: ...tive solutions to meet our world s water needs Developing new technologies that will improve the way water is used conserved and re used in the future is central to our work We move treat analyze and...

Reviews: