PAGE 16
Aquavar IPC Start-Up Genie
CentriPro
CHAPTER 8: RELAY AND ANALOG OUTPUT SETUP
This setup allows configuration of the relay and analog outputs.
• Relay Function: To modify the relay function, first press OK and use the up and
down arrows to select the correct index. Selecting [0] allows modification of
Relay 1, [1] allows modification of Relay 2. Press OK to save the index and allow
editing of the relay function. Press OK to save the Relay Function setting. The
default setting for Relay 1 is to activate on No Alarm which can be used to detect
alarms, including loss of power. The default setting for Relay 2 is to activate on
Run.
• Relay on Delay: This is the delay time from when the relay function is triggered
to when the relay transitions its state. To modify the relay delay time first press
OK and use the up and down to select the correct index. Selecting [0] allows
modification of Relay 1, [1] allows modification of Relay 2. Press OK to save the
index and allow editing of the delay time. Press OK to save the Relay on Delay
setting.
• Terminal 42 Output: Select the function of terminal 42 as an analog current
output.
• Terminal 42 Output Min: Scale the minimum output of the selected analog
signal at terminal 42, as a percentage of the maximum signal value. E.g. if OmA
of (0 Hz) is desired at 25% of the maximum output value, then program 25%.
• Terminal 42 Output Max: Scale the maximum output of the selected analog
signal at terminal 42.