background image

PAGE 4

Aquavar IPC Start-Up Genie

CentriPro

CHAPTER 1: MOTOR

Allows configuration of the motor parameters; HP, Voltage, Nominal Frequency, Nominal Speed, Motor Current, 
Motor Service Factor, and Motor Type. The Motor information for these settings are found on the motor 
nameplate. 
The Start-Up Genie will begin automatically after the initial power up (Screen 2) or it can be engaged by 
selecting Start-Up Genie under Quick Menus. First, select the language for programming (Screen 1), then you 
will be led to the Setup Selection screen. Select “Motor” in the Setup Selection screen (Screen 3) and the Genie 
will guide you through the following sequence of parameters. Press [OK] to select the parameter and enable 
editing. The highlighted area can be modified by using the up and down arrows. For numeric values with more 
than one digit, use the left and right keys to select the position within the number. Press [OK] to accept and save 
or [Cancel] to disregard the change.

SCREEN 1 

SCREEN 2 

SCREEN 3

• Motor HP: Enter the rated motor power in HP from the motor nameplate data.*
• Motor Voltage: Set the rated motor voltage from the motor nameplate data.*

• Motor Frequency: Select the motor frequency from the motor nameplate data.*
• Motor Nominal Speed: Enter the rated motor speed from the motor nameplate 

data.*

• Motor Current: Enter the rated motor current value from the motor nameplate 

data.*

• Current Limit: Set the Current Limit equal to (Service Factor Amps/Full Load 

Amps). For example, if the Motor Current (FLA) indicated on the motor nameplate 
is 5.6A and the Motor Service Factor Current (SFA) is 6.4A, enter 114% for Current 
Limit (%). Be sure to properly set the Motor Current (FLA) and Current Limit. These 
parameters will configure the motor overload protection feature.

• Motor Type: Select Submersible for borehole application or Surface for above 

ground motors. Based on selection, the following parameters will be backfilled:

PARAMETER

SUBMERSIBLE

SURFACE

Motor Speed Low Limit [4-12]

30Hz

--

Compressor Start Max Speed [1-78]

29Hz

Default

Starting Ramp Up Time [3-82]

1s

3s

Function at Stop [1-80]

Coast

Coast

Min Speed for Function at Stop [1-82]

10Hz

10Hz

• Sleep Frequency/Low Limit: Enter the minimum limit for motor speed. The motor 

speed low limit can be set to correspond to the minimum output frequency of the 
motor shaft. The motor speed low limit must not exceed Motor Frequency listed 
above.

* Changing this parameter will affect settings of other parameters.

Summary of Contents for CentriPro Aquavar

Page 1: ...AQUAVAR Intelligent Pump Controller START UP GENIE PROGRAMMING MANUAL PROGRAMMING MANUAL IM262R00...

Page 2: ...6 2 3 Duplex Control 7 2 4 Speed Control 8 2 5 Test Run Mode 8 Chapter 3 Feedback 9 Chapter 4 Setpoint 10 Chapter 5 Flow Compensation 10 Chapter 6 Pump Protection 11 Chapter 7 Digital Input 15 Chapter...

Page 3: ...cations Table 1 Setup Selection SETUP SELECTION 1 Motor 2 Application 3 Feedback Autoset 4 Setpoint 5 Flow Compensation 6 Pump Protection Setup 7 Digital Input 8 Relay and Analog Output Setup 9 Commun...

Page 4: ...tor nameplate data Motor Frequency Select the motor frequency from the motor nameplate data Motor Nominal Speed Enter the rated motor speed from the motor nameplate data Motor Current Enter the rated...

Page 5: ...ons APPLICATION TYPE Constant Pressure Pressure control using a pressure transducer or other external feedback device with analog signal Flow Control Flow control using a flow meter or other external...

Page 6: ...nalog signal CONTROL UNITS Select the appropriate control units for the application psi GPM ft etc RAMP TIME The Ramp Time is the time to transition from stop to full speed Fast 5s accelerate and 3s d...

Page 7: ...ncies too close together will cause frequent starts and stops of the lag pump LAG PUMP STOP FREQUENCY This parameter defines the speed to which system needs to drop before stopping the lag pump Settin...

Page 8: ...rrent set in par 6 10 6 12 TERMINAL 53 HIGH REFERENCE Enter the reference of feedback value that corresponds to the voltage or current set in par 6 11 6 13 MINIMUM SPEED REFERENCE Set the minimum spee...

Page 9: ...imum value programmed for that input AUTOSET For basic applications users are able to set motor information operation mode and Autoset the rest of the parameters With support for the most common contr...

Page 10: ...ive when DI 33 closed CHAPTER 5 FLOW COMPENSATION This setup allows configuration of up to 2 setpoints Flow Compensation Adjusts the setpoint based on speed flow to compensate for system head loss Is...

Page 11: ...llows the pump to stop when a no flow condition is detected A no flow condition means that the setpoint has been satisfied and the pump is running at the sleep frequency Minimum Sleep Frequency Enter...

Page 12: ...ion of the pump Typically a pump s power consumption will drop when the pump is run at no flow The graph shown below illustrates a typical pump power curve at the pump design flow and at no flow When...

Page 13: ...ng the affinity laws The No Flow Power Calibration Set up is now complete The power data can be saved by pressing OK and then the down arrow If any issues were encountered during the calibration proce...

Page 14: ...ll trigger the Under Pressure Function This value is set as a of Maximum Reference Feedback Under Pressure Difference Example Given Under Pressure Delay 10 seconds Under Pressure Difference 10 Setpoin...

Page 15: ...4 20mA 0 Torque Limit 4 16 Torque Limit Motor Mode 102 Feedback 200 200 to 200 of 20 14 Maximum Reference Feedb 0 20 mA 135 Torque 0 nom 4 20mA 0 Motor rated torque 103 Motor Current 0 Imax 0 Inverte...

Page 16: ...activate on Run Relay on Delay This is the delay time from when the relay function is triggered to when the relay transitions its state To modify the relay delay time first press OK and use the up an...

Page 17: ...the minimum delay time between receiving a request and transmitting a response This is used for overcoming modem turnaround delays Maximum Response Delay Specify the maximum permissible delay time be...

Page 18: ...asing this value optimizes polling for the token Control Timeout Time enter the maximum time expected to pass between the receptions of two consecutive telegrams If this time is exceeded it indicates...

Page 19: ...ther drive select Yes to copy setup to LCP then transfer LCP to another drive and select Copy from LCP in the Start Up Genie CHAPTER 11 COPY FROM LCP LOCAL CONTROL PANEL Allows all of the controlled p...

Page 20: ...tive solutions to meet our world s water needs Developing new technologies that will improve the way water is used conserved and re used in the future is central to our work We move treat analyze and...

Reviews: