PAGE 8
Aquavar IPC Start-Up Genie
CentriPro
2.4. Speed Control: Receives a speed command from an external source.
• SPEED REFERENCE SOURCE: Set the source for the speed command. For
analog inputs 53 and 54. Be sure to properly set the configuration switches
A53 and A54 behind the keypad. Switch set to “I” for mA transducer; switch
set to “U” for voltage transducer”
• TERMINAL 53 LOW REFERENCE: Enter the reference of feedback value
that corresponds to the voltage or current set in par. 6-10/6-12
• TERMINAL 53 HIGH REFERENCE: Enter the reference of feedback value
that corresponds to the voltage or current set in par. 6-11/6-13
• MINIMUM SPEED REFERENCE: Set the minimum speed that can be
commanded by the Speed Reference Source.
• MAXIMUM SPEED REFERENCE: Set the maximum speed that can be
commanded by the Speed Reference Source.
2.5. Test Run Mode: Ramps the motor to a specific speed.
• TEST RUN SPEED: Set the Test Run Speed as the speed the pump will run
when test mode is enabled.
• TEST RUN RAMP TIME: Set the Test Run Ramp Time as the time ramp used
when starting and stopping the pump in Test Run Mode.
CHAPTER 2: APPLICATION
(continued)