Specifications
MODEL NUMBER
X90-2S50k
X90-2S70k
X90-2S100k
X90-2S140k
CAPACITY
Power rating
50kVA/50kW
70kVA/70kW
100kVA/100kW
140kVA/140kW
CABINET
CAPACITY
X90-2S UPS: power modules
Up to 140kW (2 x 70kW) or up to 100kVA (2 x 50kW)
X90-2S UPS: battery modules
4, 8, 12, 16 or 20 battery modules
X90-BC: battery modules
Up to 36 additional battery modules
INPUT
Voltage / frequency nominal
480VAC (3W), 50/60Hz auto-sensing
Voltage / frequency range
329
–
520VAC (L-L), 40
–
70Hz
OUTPUT
Voltage
480VAC (3W)
Frequency
40
–
70Hz
Efficiency
Up to 96% online mode or 99% ECO mode
Overload capacity
105%-110% for 60min; 110%-125% for 10min; 126%-150% for 1min; >150% for 200ms
BATTERY SYSTEM
Nominal voltage
+/-240VDC
Charge Current (programable)
18A
18A
36A
36A
DIMENSIONS &
WEIGHTS
UPS & Battery Cabinet (W x D x H)
23.6 x 42 x 79 in / 357 lbs (UPS) / 23.6 x 42 x 79 in 878 lbs (BC)
Power & Battery module (W x D x H)
4.2 x 28 x 6 in / 104 lbs (PM) 17.2 x 29.5 x 5.25 in / 73 lbs (BM)
ENVIRONMENT
Temperature
0
–
40°C (32
–
104°F)
Altitude
5,200 ft above sea level
Audible noise (typical)
< 69dBA at 1m
APPROVALS
UL-1778, cUL, FCC A, RoHS, TAA
WARRANTY
2 years (USA and Canada)
COMMUNICATIONS INTERFACE
RS-232, EPO, intelligent slot for optional cards (Web/SNMP, Relay, Modbus)
INCLUDED IN BOX
User manual, RS-232 cable, unloading ramp, ViewPower Software
AVAILABLE OPTIONS
External Maintenance bypass, Battery Temperature Sensor
Summary of Contents for X90-2S
Page 12: ...2 6 1 Mechanical Data Dimensions Width Depth Height 600mm 1065m 2010mm Figure 2 8 Dimensions...
Page 15: ...Figure 2 13 Terminal Blocks...
Page 17: ...Off There is neither a fault nor an alarm...
Page 22: ......
Page 37: ......
Page 39: ...Step 7 Switch ON the output breaker Q3 AC startup procedure is complete...
Page 42: ......
Page 53: ...Figure 4 6 Control screen page...
Page 55: ...Figure 4 9 System Measurement Screens...
Page 56: ...Figure 4 10 Module Measurement Screens...
Page 88: ......