2.10 Power Cable
Please follow the local wiring regulations. Consider environmental conditions and
refer to IEC60950-1.
2.10.1 AC input and output nominal current and cable fixation force.
Power rating
50KVA 100KVA 70KVA 140KVA
Output Current (A)
60
84
120
168
Mains Input Current (A)
62
87
124
174
Bypass Input Current (A)
60
84
120
168
Fixation torque force (lb-in)
60
60
60
60
2.10.2 DC input nominal current and cable fixation force.
Power rating
50KVA 100KVA 70KVA 140KVA
DC Current (A)
110
154
220
309
Fixation torque force (lb-in)
60
60
60
60
2.11 Wiring
WARNING:
⚫
Before connecting any wire, make sure the AC input and battery power are completely cut off.
⚫
Make sure Main Breaker (Q1), Maintenance Breaker (Q2), Output Breaker (Q3) and battery
breaker are all in the
OFF
position.
⚫
The power cables MUST enter the cabinet from top of the cabinet. Or the cables will block the
cooling ventilation and result in over temperature failure.