Fault! <41>Over temp
Over temperature
Fault! <42>DSP commu fail
DSP communication failed
Fault! <43>Overload
Heavy overload causes UPS to fault
Fault! <45>Charger error
As stated
Fault! <46>Incorrect UPS set
Incorrect UPS setting
Fault! <47>DSP&MCU commu fail
MCU communication failed
Fault! <49>In&out phase incomp
Input and output phase error
Fault! <61>BYP SCR SC
Bypass SCR short circuited
Fault! <62>BYP SCR open
Bypass SCR open
Fault! <63>INV R wave abnormal
Voltage waveform abnormal in R phase
Fault! <64>INV S wave abnormal
Voltage waveform abnormal in S phase
Fault! <65>INV T wave abnormal
Voltage waveform abnormal in T phase
Fault! <66>CT saturation
As stated
Fault! <67>BYP out SC
Bypass output short circuited
Fault! <68>BYP out line SC
Bypass output line to line short circuited
Fault! <69>INV SCR SC
Inverter Relay short circuited
Fault! <6C>Bus-VOL dec fast
BUS voltage drops too fast
Fault! <6D>CUR detect err
Current sampling value error
Fault! <6E>SPS Power fault
SPS Power fault
Fault! <6F>BATT reversal
Battery polarity reversed
Fault! <71>R PFC IGBT fault
PFC IGBT over-current in R phase
Fault! <72>S PFC IGBT fault
PFC IGBT over-current in S phase
Fault! <73>T PFC IGBT fault
PFC IGBT over-current in T phase
Fault! <74>R INV IGBT fault
INV IGBT over-current in R phase
Fault! <75>S INV IGBT fault
INV IGBT over-current in S phase
Fault! <76>T INV IGBT fault
INV IGBT over-current in T phase
Fault! <77> ISO Over temp
Isolation transformer over temperature
Fault! <79> Power Module Connect Fail As stated
Warning! <01> BATT open
Battery not connected
Warning! <02> IP N loss
Input Neutral loss
Warning! <03> IP site fail
Input site failed
Warning! <04> Line phase error
As stated
Warning! <05> Bypass phase error
As stated
Warning! <06> Bypass FRE unstable
Bypass frequency unstable
Warning! <07> BATT over charge
Battery over charge
Warning! <08> BATT low
Battery voltage is too low.
Warning! <09> Overload warning
As stated
Warning! <0A> Fan lock warning
As stated
Warning! <0B> EPO active
As stated
Warning! <0D> Over temperature
As stated
Warning! <10> L1 IP fuse fail
L1 Input fuse failed
Warning! <11> L2 IP fuse fail
L2 Input fuse failed
Warning! <12> L3 IP fuse fail
L3 Input fuse failed
Warning! <21> Line connect dif
Line connect different
Warning! <22> Bypass connect dif
Bypass connect different
Warning! <24> Par INV vol dif
Parallel output voltage setting different
Warning! <33> Lock BYP OL 3 times
Locked in bypass after overload 3 times in 30 min
Summary of Contents for X90-2S
Page 12: ...2 6 1 Mechanical Data Dimensions Width Depth Height 600mm 1065m 2010mm Figure 2 8 Dimensions...
Page 15: ...Figure 2 13 Terminal Blocks...
Page 17: ...Off There is neither a fault nor an alarm...
Page 22: ......
Page 37: ......
Page 39: ...Step 7 Switch ON the output breaker Q3 AC startup procedure is complete...
Page 42: ......
Page 53: ...Figure 4 6 Control screen page...
Page 55: ...Figure 4 9 System Measurement Screens...
Page 56: ...Figure 4 10 Module Measurement Screens...
Page 88: ......