VESDA by Xtralis
VESDA VLC-605 Installation Guide
www.xtralis.com
27
11 Trouble Codes
The VLC-605 device monitors itself for many internal trouble conditions. However unlikely these may be when
they do occur the VLC-605 will signal the AutoPulse control panel to which it is connected. The VSC program
would be used to retrieve the active event information from the VLC-605 device.
The following table lists the trouble numbers, description of the trouble and the corresponding message that
the AutoPulse control panel will display on its LCD.
VSC Trouble No.
Description of Trouble
AutoPulse control panel LCD message
0
Aspirator trouble
No Answer Trouble
3
Head processor trouble
Sensor Trouble
4
Filter has been removed
No Answer Trouble
8
Aspirator regulation trouble
No Answer Trouble
11
Filter clogging warning
Sensor Trouble
12
Default Configuration
No Answer Trouble
14
Default flow sensor calibration
No Answer Trouble
15
Power Supply Monitor input active
Sensor Trouble
22
Inlet flow sensor trouble
Sensor Trouble
23
Preamp trouble
No Answer Trouble
29
Default Manufacturer Configuration
Sensor Trouble
33
PIN trouble
Sensor Trouble
34
Head Configuration trouble
Sensor Trouble
36
Event log trouble
Sensor Trouble
37
Head Calibration trouble
No Answer Trouble
51
Urgent high airflow inlet pipe
Sensor Trouble
52
Minor high airflow inlet pipe
Sensor Trouble
53
Minor low airflow inlet pipe
Sensor Trouble
54
Urgent low airflow inlet pipe
Sensor Trouble
56
RTC trouble
Sensor Trouble
59
Test Fault
Sensor Trouble
65
Software version trouble
No Answer Trouble
73
Urgent Filter clogging warning
No Answer Trouble
74
Raw flow too high
Sensor Trouble
75
Normalization has failed
Sensor Trouble
76
Filter replaced but not acknowledged
Sensor Trouble
77
Normalization in progress
Sensor Trouble
81
Default Configuration
Sensor Trouble
Table 11-1: VLC-605 Trouble codes / AutoPulse control panel messages
Summary of Contents for VESDA VLC-605