VESDA VLC-605 Installation Guide
VESDA by Xtralis
32
www.xtralis.com
Assembly
1. Insert a new air filter cartridge (A).
2. Tighten filter screw (B).
3. Reset the filter counter by connecting a LCD
programmer or a PC with VSC software to the
programming socket.
4. Using a LCD programmer (VN version only):
a. Enter your user level and PIN number to Log
ON to the detector.
b. Initiate the New Filter command located
under the Filter menu.
5. Using a PC only (Applicable to RO version) or
Using a PC with a PC-Link HLI (Applicable to VN
version only):
a. Enter your user level and PIN number to Log
ON to the detector.
b. Initiate Reset Filter Settings command
located under the Device menu.
6. Close up the detector.
12.5 Replacing the Aspirator
Disassembly
1. Remove the four screws (A) securing the termination card.
2. Disconnect the aspirator cable loom from the connector on the aspirator.
3. Gently pull out termination card (B) from interface card (connected behind).
4. Be careful not to dislodge any wires connected to the termination card.
5. Leave the termination card suspended by its wires.
6. Pull off the air hose from aspirator pipe (D).
7. Undo three Philips head screws securing aspirator (E). Screws are captive and do not come off the
aspirator.
8. Turn aspirator anti-clockwise (F) using the exhaust port as the pivot point.
9. Push aspirator upward (G) and remove.
Assembly
1. Check the new aspirator has a gasket on the inlet flange and three attached screws
2. Wipe manifold outlet flange surface (J) if dirty.
3. Do the reverse of disassembly
4. Secure aspirator with three screws
5. Connect removed air hose to pipe on aspirator. Ensure a tight fit over the pipe.
Summary of Contents for VESDA VLC-605