“Truth table” of the external Sensor
External Sensor, Motion Detector
Parameter in the Setup Menu:
E=1
, F=x, C=x, L=x,
S=1
, P=x, I=x, A=x, H=x (x= 0 or 1)
Measured
Load
Programmed
Value in PE
Breaker Signal
Motion Detector
Switching Output
Minimum Load
(KL3)
Comment
17kg
40kg
High/open
Activated
Load measurement detects minimum
load, motion detector detects no motion
25kg
40kg
Low (0V)
Not activated
Load measurement detects minimum
load, but motion detector detects motion
(person inside the car)
80kg
40kg
High/open
Not activated
Load measurement detects no minimum
load, motion detector detects no motion
(e.g. packet or palett is inside the car)
80kg
40kg
Low (0V)
Not activated
Load measurement detects no minimum
load, motion detector detects motion
(person inside the car)
The CLMI can connect the breaker signal of an external motion detector to the measured load. If the
param
eter “S” is set to 1, the input (X5, Pin1) of the external sensor will be activated. The switching output
which shows the status “Minimum Load” will only be activated if a logical 1 is present at this input.
Electrical installation
Advices:
Before the commissioning, control if the
mains voltages are correctly chosen.
Please note the relevant ground and
isolation instructions.
Switch electric loads over 20mA with the
relay contacts, not with the control outputs.
If the CLMI is operated with mains voltage,
the 24V terminal (X1, Pin 1) as supply
output may be loaded with maximal 70 mA.
The terminal might serve to supply an
external overload indicator with 24V.