Programmable Functions 

 

Setup Menu 

 

Basic Menu 

Function 

Command 

Range of Values, Comment 

P0 

(Parameter 0) 

Teach-in zero point. 
Assigning a currently 
measured load to a 
certain zero point. 
 
 

Only executing when the car is empty. 
 
Allowed range: -99 to 999 
Suggestive range: -10 to 100 
 
(

→ s. paragraph “Setup Menu”, “Floor Detection”) 

(*) P0_ 

(Parameter 0 bottom) 

Teach-in zero point at 
lowest floor. 
Assigning a currently 
measured load to a 
certain zero point. 
 
 

Only executing when the car is empty. 
 
Allowed range: -99 to 999 
Suggestive range: -10 to 100 
 
(

→ s. paragraph “Setup Menu”, “Floor Detection”) 

(*) P0

‾ 

(Parameter 0 top) 

Teach-in zero point at 
highest floor. 
Assigning a current 
measured load to a 
certain zero point. 
 
 

Only executing when the car is empty. 
 
Allowed range: -99 to 999 
Suggestive range: -10 to 100 
 
(

→ s. paragraph “Setup Menu”, “Floor Detection”) 

(*) PE 

 

Operating threshold for 
relay contact KL3 
(Car Empty) 
 

Allowed range: -99 to 999 
Suggestive range: 5..25% of nominal load 
 
(

→ s. paragraph “Setup Menu”, “Floor Detection”) 

P1 

(Parameter 1) 

Not used 

Allowed range: -99 to 999 
Suggestive range: 0 (not used) 
 

P2 

(Parameter 2) 

Operating threshold for 
relay contact KL1 
(full load) 
 

Allowed range: -99 to 999 
Suggestive range: 100% of nominal load 

P3 

(Parameter 3) 

Operating threshold for 
relay contact KL2 
(overload) 
 

Allowed range: -99 to 999 
Suggestive range: 120% of nominal load 

P4 

(Parameter 4) 

Teach-in nominal load. 
Assigning the currently 
measured load to a 
certain displayed value. 
 

Only executing when the car is full. 
 
Allowed range: -99 to 999 
Suggestive range: Nominal load, i.e. real weight of 
the load in kg inside the car. 

(*) 

Optional Parameter must be activated in the setup menu. 

     The switching polarity of KL3 is always inverted to the switching polarity of KL1 and KL2. 

 

 

Function 

Command 

Range of Values, Comment 

(Minimum load 
measuring) 

Activates the Parameter 
PE 

0

 = Relay contact inactive, PE not programmable 

1 = Relay contact active, PE programmable. 
  

(Floor detection) 

Activates the floor 
detection and the 
travelling cable 
compensation 
 

0

 = Floor detection inactive 

1 = Floor detection active, P0 must be taught-in twice 
Once at lowest floor, once at highest floor. 
 

(Coding) 

Floor information is read 
in binary or Gray code 
 

0

 = Binary coded 

1 = Gray coded 

(Logic Polarity of 
coding) 
 

Floor information and 
Synch is low or high 
active 
 

0

 = 5..24V corresponds logic 1 (1 active)  

1 = 0V corresponds logic 1 (0 active) 
 

(External sensor for 

“Car 

Empty

”) 

Activates sensor at X5 
(

→ s. paragraph “Input 

and Output“) 
 

0

 = Breaker signal is not processed 

1 = Breaker signal is processed 
(

→ s. paragraph “External Sensor”) 

 

(Polarity of the switching 
output X1 and relay at 
X3) 

Inverts the polarity of the 
digital switching outputs 
X1 and the relay at X3 

0

 = normal polarity, achieved operating threshold 

sets output to plus, relay energizes. 
1 = inverted polarity, achieved operating threshold 
sets output to 0V, relay de-energizes. 
 
 

(Polarity load measuring 
sensor at X2) 

Inverts the polarity of the 
signals of the load 
measuring sensor at X2 

0

 = normal polarity, sensor signal becomes more 

positive during loading of the car 
1= inverted polarity, sensor signal becomes more 
negative during loading of the car  
 

(Response delay of 
 KL 2) 

Delays the operating of 
KL2 (overload) during 
programmed time 

Adjustable from 99 Digits, relative 0 to 9.9 seconds. 
Recommended value: 1 second (10 Digits) 

(Switching hysteresis for 
all outputs) 
 

Switching hysteresis in 
kg for all outputs. 

Adjustable from 0..99kg. 
Recommended value: 10..15kg. 
Prevents the 

“oscillating“ of the relay contacts. 

(

→ consult the paragraph "Troubleshooting“) 

 
Please note! 

If the functions (E, F, P, I) are modified in the setup menu, so P0 und P4 must be compulsory taught-in again. 
This signifies the car must be load with the nominal load again. 
The blinking of the left zero point warns you that a new teach-in is required. 
If the change is manually undone in the setup menu, so another teach-

in won’t be required. 

But this isn’t possible anymore when you have left the setup menu before without undoing the change. 

Default settings

 of the setup menu are marked 

bold

 in the list above. 

 
 

Summary of Contents for CLMI X-232

Page 1: ...Some reflections to the minimum load measurement 4 Background information about the floor detection 4 Truth table of the external sensor 5 Electrical installation 5 Typical installation minimum confi...

Page 2: ...control unit and they send the signal of the load to the control unit The relay contacts are provided for Car Empty full load 90 group travelling reduces intermediate stops overload These values are...

Page 3: ...tion Boxes for two sensors 5kg Yes without restrictions Below the ground X 133 Sxx Extension cable Junction Boxes for two sensors 2kg Yes without restrictions heavily depends on the installation If mo...

Page 4: ...e biggest elongation can reduce the error If possible use a very elastic yoke Rank 5 Another easy and robust method This solution suits in every case where no suitable yoke is available Beside the alr...

Page 5: ...kg Low 0V Not activated Load measurement detects no minimum load motion detector detects motion person inside the car The CLMI can connect the breaker signal of an external motion detector to the meas...

Page 6: ...Manuel_X_232_EN 6 13 27 01 2016...

Page 7: ...propriate input of the control unit After commissioning the CLMI with the relay contact reports the overload to the control unit Beside the basic functions the CLMI X 232 offers some expansions Compen...

Page 8: ...and alarm output according to electrical installation Turn on the supply the display shows a random number now Preparation Acquaint yourself with functions in the setup menu and set these functions re...

Page 9: ...sulation class must correspond to the switching voltage Relay contacts 3 relay contacts normally open NO Galvanically separated Pin 1 C KL1 Full load Pin 2 NO KL1 Full load Pin 3 C KL2 Overload Pin 4...

Page 10: ...detection Activates the floor detection and the travelling cable compensation 0 Floor detection inactive 1 Floor detection active P0 must be taught in twice Once at lowest floor once at highest floor...

Page 11: ...zation you can restore the last saved value by pressing UP and DOWN at the same time s paragraph FAQ 60 seconds after the last key pressing the device returns to the display mode Any taken change will...

Page 12: ...nd off without requiring a calibration again s paragraph Setup Menu Q How do I have to set the zero point if I have to be on the car while I operate A Consult the paragraph Commissioning Variant 1 and...

Page 13: ...ly eliminated At the yoke you can reduce the hysteresis by mounting a second sensor at another yoke profile The correct mounting of the sensor is the general condition no color at the bearing areas sc...

Reviews: