Troubleshooting 
 

 

Warnings 

 

Q: I try to set P4 by pressing UP/DOWN but it always appears 

“Err“.

 

A: You have tried to calibrate with a too low load or with an unavailable span. Load the car with the payload or control the sensor.  
You can increase the sensor signal by loading the cabin with 120% of payload. It is understood that also P4 has to be increased to 
120%.  
You have tried to teach-in 

P4 although Bit6 at X4(synchronization) is set to “High“. This means “Measuring Stop“ and no 

measurement will be executed. 
You tried to calibrate P4 with a negative signal span. Check polarity settings of sensor and/or X-232. 

 
Q: The alarm contacts are switching during the ride.

 

A: Short fluctuations of the measured values can be disabled by increasing the response delay by a few seconds and by adding some 
kilograms to the hysteresis value. (

→ s. paragraph “Setup Menu“) 

Alternative: Connect the output "Measuring Stop" to your control unit. In this way, you can synchronize the CLMI to the elevator. E.g. 
You can only accept measurements as long as the door is open. 
 

Q: 

The minimum contact doesn’t switch reliably

 

A:  If  the  switching  hysteresis  (

→  Setup  Menu) is  set too large, it  may  occur  that  the  hysteresis is  as large  as  the  set limits  for  the 

minimum load measuring. The CLMI cannot clearly determine the status. Reduce the hysteresis by maximal 50% of the value which 
was programmed in 

“PE“. 

 

Q: 

The minimum contact doesn’t switch.

 

A: If the parameter 

“S“ (external sensor) is set to 1, you must pull down Pin 1 at X5 to 0V, thereby KL3 will be activated. If there is a 

cable break or defect motion detector

, KL3 won’t be activated. 

As a general rule, the contacts do only switch, if ALL parameters have been programmed. 
 

Q: The zero point is fluctuating.

 

A: Depending on the chosen strategy of load measuring, the measuring is more or less immune to any kind of fault. Load measuring 
at the yoke or fixed point requires an almost frictionless guidance of the car to generate a repeatable zero point. If you can realize a 
load measuring below the ground, the effect of the friction can be completely eliminated. 
At the yoke, you can reduce the hysteresis by mounting a second sensor at another yoke profile. 
The correct mounting of the sensor is the general condition (no color at the bearing areas, screws well tied up) 

 

Q: After a certain time my display shows nothing except a blinking decimal point. 

A: After 30 minutes idle time the display changes to the standby-mode. If you press any key, the display will show plaintext again. 

 

Q: During the installation, I have sometimes realized aberrations of the zero point which slowly disappear.

 

A: The CLMI has an approximation process of the zero point. Is the measured load closer to 40kg than to zero and when this 
meas

ured load doesn’t change for two hours, so the CLMI will slowly adopt the 40kg as new zero point. This process would last a few 

days, so the CLMI evaluates an optimal zero point. Long-term errors due to drift or continually mechanical abrasion can be 
compensated. 

 

Q: I have two sensor inputs at the CLMI. How does the CLMI interpret the signal from these two sensors?

 

A: The signal of these two sensors is averaged. Therefore all errors, working in the opposite direction are compensated.

 

 
 

 

It is understood, that the setup, configuration and operation may only be done by qualified personnel. 
The series X-232 load indicators must not be used in life-supporting applications. The series X-232 load indicators 
must not be used in safety-critical applications. 
 
If you do not pay attention to this security hints, serious damages can be provoked. 

 

 

General rules for installation 
 

 

Maintenance, Repairing 

Pay attention all the time and mainly during your installation process to all legal rules and security-hints to prevent any accident. Do 
always  separate  the  signal  lines  from  power  lines  (drives,  converters)  and  do  never  interrupt  the  signal  lines  unless  you  use 
designated junction boxes. (X-914) 
Tie cable shield (braid) at both ends to a proper ground. Tie all machine  parts to one well defined potential by using massive copper 
wires.  Prevent  at any  case  that  a  ground  current  flows  over  the  cable  shield.  Prevent  different  potentials in  your  machine,  they  will 
create currents which can be hardly controlled. 

 

 
 
 
The  devices  of  the  serie  X-232  do  not  contain  any  serviceable  parts.  Any  repairing  is  done  exclusively  by  the 
manufacturer 

 

Summary of Contents for CLMI X-232

Page 1: ...Some reflections to the minimum load measurement 4 Background information about the floor detection 4 Truth table of the external sensor 5 Electrical installation 5 Typical installation minimum confi...

Page 2: ...control unit and they send the signal of the load to the control unit The relay contacts are provided for Car Empty full load 90 group travelling reduces intermediate stops overload These values are...

Page 3: ...tion Boxes for two sensors 5kg Yes without restrictions Below the ground X 133 Sxx Extension cable Junction Boxes for two sensors 2kg Yes without restrictions heavily depends on the installation If mo...

Page 4: ...e biggest elongation can reduce the error If possible use a very elastic yoke Rank 5 Another easy and robust method This solution suits in every case where no suitable yoke is available Beside the alr...

Page 5: ...kg Low 0V Not activated Load measurement detects no minimum load motion detector detects motion person inside the car The CLMI can connect the breaker signal of an external motion detector to the meas...

Page 6: ...Manuel_X_232_EN 6 13 27 01 2016...

Page 7: ...propriate input of the control unit After commissioning the CLMI with the relay contact reports the overload to the control unit Beside the basic functions the CLMI X 232 offers some expansions Compen...

Page 8: ...and alarm output according to electrical installation Turn on the supply the display shows a random number now Preparation Acquaint yourself with functions in the setup menu and set these functions re...

Page 9: ...sulation class must correspond to the switching voltage Relay contacts 3 relay contacts normally open NO Galvanically separated Pin 1 C KL1 Full load Pin 2 NO KL1 Full load Pin 3 C KL2 Overload Pin 4...

Page 10: ...detection Activates the floor detection and the travelling cable compensation 0 Floor detection inactive 1 Floor detection active P0 must be taught in twice Once at lowest floor once at highest floor...

Page 11: ...zation you can restore the last saved value by pressing UP and DOWN at the same time s paragraph FAQ 60 seconds after the last key pressing the device returns to the display mode Any taken change will...

Page 12: ...nd off without requiring a calibration again s paragraph Setup Menu Q How do I have to set the zero point if I have to be on the car while I operate A Consult the paragraph Commissioning Variant 1 and...

Page 13: ...ly eliminated At the yoke you can reduce the hysteresis by mounting a second sensor at another yoke profile The correct mounting of the sensor is the general condition no color at the bearing areas sc...

Reviews: