background image

 

 

 

1. Check  there  are  no  buried  pipes  or  cables  e.g. 
electricity, gas, water behind the switch location (In 
the panel or above the ceiling). 

2. Lay  in  the  cable  from  the  isolating  switch  to  the  fan 
location via the on/off switch if required. 
3. Lay in the cable from the isolating switch to the point 
of connection to the mains supply. 

 
WARNING: DO NOT MAKE  ANY CONNECTIONS TO 
THE ELECTRICAL SUPPLY AT THIS STAGE. 

4. Install  the  isolating  switch  and  the  on/off  switch  if 
required.  

5. 

Make  all  connections  within  the  isolating  switch  and 

the on/off switch if required. 

 

Note: Switches must be situated so that they cannot 
be  touched  by  persons  making  use  of  the  bath  or 
shower. 

  

For Australia only

  

These models are permanently connected to the supply 
and  operation  is  controlled  by  a  remote  switch.  They 
should  be  directly  wired  to  the  supply  through  an 
approved 10A wall mounted surface switch with at least 
3mm clearance between contacts.  

 

 

 

If  working  above  ground  floor  level,  appropriate 
safety precautions must be observed. 
WARNING:  EYE  PROTECTION  MUST  BE  WORN 
DURING ALL DRILLING OPERATIONS. 

 

 

For Installing in a wall 
1. Check  there  are  no  buried  pipes  or  cables  in  the 
wall  or  obstructions  on  the  outside  e.g.  electricity, 
gas, water.  

2. Make sure that the centre of the hole is located at least 
200mm from the edge of the wall. 
3. Mark  the  outline  of  the  hole  on  the  wall  (for  hole 
dimensions see Fig A). 
4. Drill pilot holes around edge of the cutting line. 
5. Cut through the plaster using a hammer and chisel. 
6. Cut through the inner wall using a cold chisel or brick 
bolster. Do not cut right through. 
7. Go  outside  and  cut a  hole  in  the  outer  wall  ensuring 
alignment  

 

 

 

1. Remove the inner grille assembly by removing the two 
screws Fig. F (10) securing the inner grille assembly to 
the fan mounting box.  
2. Remove the two screws securing the fan assembly to 
the fan mounting box. 

 

 

 

If  working  above  ground  floor  level,  appropriate 
safety precautions must be observed.

  

 

1. Insert the two colour matching Screw Covers (packed 
separately)  in  the  fixing  holes  of  the  Outer  Grille,  the 
fixing holes are not used on the outer grille. 

 

2. Secure  the  two  ladder  strips  to  the  Outer  Grille  by 
positioning  them  over  the  hook  mouldings  (packed 
separately) and snapping these into position (Fig. B). 
3. Hold  the  Outer  Grille  up  to  the  outside  of  the  wall 
ensuring the ladder strips protrude through to the interior. 
4. Offer  up  the  fan  mounting  box  to  the  inner  wall  face 
and locate ladder strips into their location fixings (Fig. D). 
5. Pull the ladder strips through, locate the wall box in the 
wall  and  screw  worm  screws  into  position. 

Do  not

 

overtighten  the  screws

.  Cut  away  any  excess  ladder 

strip remaining. If necessary, apply a sealing mastic (not 
supplied)  to  the  flanges  of  the  Fan  Mounting  Box  and 
Outer  Grille. This  will  provide  additional  seals  and  take 
out any unevenness on both wall faces. 
6. Assemble  wall  tube  by  slotting  the  four  sections 
together (Fig. E) 
7. Push  the  wall  tube  through  the  hole  in  the  fan 
mounting box and locate on the Outer Grille. 
8. The cavity  wall tube must be cut flush  with the  inner 
face of the fan mounting box. Mark off and cut away any 
excess wall tube and re-install. When installed, the wall 
box  must  slope  slightly  downwards  towards  the  outer 
grille. 

9. 

Position and secure the fan duct assembly into the fan 

mounting  box,  using  the  fixing  screws. 

Do  not 

overtighten the screws. 

 

 

 

1. 

Wire the switch cable into the fan’s terminal connector 

as shown in Fig. C.  

a. 

If  the  Fan  is  wired  from  above,  remove  the  fan’s 

Terminal cover and feed the cable through the top cable 
entry. Ensure the outer sheath of the cable is retained in 
the labyrinth Fig. C.  

b. 

If  wiring  from  the  rear,  remove  the  fan’s  terminal 

cover and rear entry knockout, feed the cable through the 
knockout. 
2. Refit and secure the terminal cover. 

3. 

Refit  the  inner  grille  to  the  fan  mounting  box,  using 

fixing screws Fig. F (10). 

Do not overtighten screws. 

4. Insert two colour matching screw covers in the fixing 
holes in the inner grille. When removing the covers, place 
a 3mm blade electrician’s  screwdriver into the slot and 
lever off the cover. 
5. 

Switch off the mains electrical supply and remove 

fuses.

  

6. Connect  the  cable  from  isolation  switch  to  the 
electrical supply wiring. 
7. Replace the fuses, and switch on the mains electrical 
supply.  

For  fixed  wiring  circuits  the  protective  fuse  for  the 
appliance must not exceed 5A. 

 

  

 

This fan is single speed and non-reversible (extract only). 

Switch operated: 

 To  switch  on  and  off,  use  the  switch  on  the  wall  or 

ceiling. 

 The  shutters  have  a  time  delay  of  up  to  1  minute  on 

opening, and up to 3 minutes on closing. Activated by 

4.  Installing the switches and cables 

5.  Preparing the hole 

6.  Separating the inner grille and fan from mounting 

box 

7.  Mounting the fan mounting box 

8.  Wire the electrical connections 

9.  Operating the fan 

Summary of Contents for WX6EC - 071422

Page 1: ...Internal External Wall Panel Fan WX6EC 071422 Installation and maintenance instructions Retain for future reference ...

Page 2: ...B C A E D ...

Page 3: ...G H1 H3 H4 H2 F ...

Page 4: ...ring in accordance with the wiring regulations If metal switch boxes are used earthing regulations must be followed Circular 2 core cable of a minimum 0 75mm with a diameter not less than 5 5mm Product is double insulated and does not require an Earth 6mm blade large screwdriver 3mm blade electrician s screwdriver and No 1 2 Pozidriv screwdrivers Masonry drill hammer chisel Extendible wall tube WK...

Page 5: ... wall ensuring the ladder strips protrude through to the interior 4 Offer up the fan mounting box to the inner wall face and locate ladder strips into their location fixings Fig D 5 Pull the ladder strips through locate the wall box in the wall and screw worm screws into position Do not overtighten the screws Cut away any excess ladder strip remaining If necessary apply a sealing mastic not suppli...

Page 6: ... Before cleaning isolate the fan completely from the mains supply Allow 3 minutes for the impeller to stop and the powered shutter to close 2 Remove the inner grille and back draught shutter by removing the two screw covers and the screws securing the inner grille assembly to the fan mounting box Fig F 10 To remove the backdraft shutter lay the inner grille face down and pull shutter assembly upwa...

Page 7: ... fonctionnement à interrupteur à distance Fonctionnement à vitesse unique d extraction Un moyen de déconnection à tous les pôles doit être incorporé au câblage fixe conformément aux règlements de câblage Si des boîtes de commutation métalliques sont utilisées les règlements de mise à la terre doivent être respectés Câble circulaire à 2 conducteurs d un minimum de 0 75 mm avec un diamètre d au moin...

Page 8: ... veillant à ce qu il soit aligné 1 Retirez l ensemble de la grille intérieure en retirant les deux vis figure F 10 en attachant l ensemble de la grille intérieure au boîtier de montage du ventilateur 2 Retirez les deux vis retenant l ensemble du ventilateur au boîtier de montage du ventilateur Si vous travaillez au dessus du niveau du sol vous devez prendre des précautions de sécurité appropriées ...

Page 9: ...l obturateur voir la figure G Pour complètement fermer les obturateurs et arrêter tout tirage arrière 4 Tirez le loquet d évent à faible écoulement d air vers vous jusqu à ce qu il s enclenche en place 5 Remettez la grille intérieure et l obturateur de tirage arrière en veillant à ce que le levier d actionnement soit à la position complètement vers le bas UN ÉLECTRICIEN QUALIFIÉ DOIT EFFECTUER TOU...

Page 10: ...verschlüsse Für Fernschalterbetrieb Eingeschwindigkeits Extraktionsbetrieb In der festen Verdrahtung ist eine allpolige Trennmöglichkeit nach den Verdrahtungsregeln einzubauen Bei Verwendung von Metallschaltkästen sind die Erdungsvorschriften zu beachten Rundes 2 adriges Kabel mit einem Durchmesser von mindestens 0 75 mm und einem Durchmesser von mindestens 5 5 mm Produkt ist doppelt isoliert und ...

Page 11: ...auben Abb F 10 entfernen mit denen die Innengitterbaugruppe am Lüftermontagekasten befestigt ist 2 Entfernen Sie die beiden Schrauben mit denen die Lüfterbaugruppe am Lüftermontagekasten befestigt ist Bei Arbeiten über Grund sind angemessene Sicherheitsmaßnahmen zu befolgen 1 Setzen Sie die beiden farblich passenden Schraubenabdeckungen separat verpackt in die Befestigungslöcher des Außengitters e...

Page 12: ... Rückzug 4 Ziehen Sie die Rieselbelüftungssperre zu sich bis sie einrastet 5 Setzen Sie das Innengitter und den Rückzugverschluss wieder ein und stellen Sie sicher dass sich der Betätigungshebel in der Position vollständig unten befindet SÄMTLICHE REINIGUNGSARBEITEN SIND VON EINER ELEKTROFACHKRAFT DURCHZUFÜHREN HINWEIS DER LÜFTER ARBEITET BEI ABGENOMMENER INNENGITTERBAUGRUPPE WEITER DAHER MUSS ER ...

Page 13: ...vengono utilizzate scatole per interruttori metalliche devono essere seguite le normative sulla messa a terra Cavo bipolare circolare di un minimo di 0 75mm con un diametro non inferiore a 5 5mm il Prodotto ha un doppio isolamento e non richiede una messa a terra Cacciavite a taglio svasato 6mm cacciavite per elettricisti a taglio svasato 3mm e cacciaviti a croce Pozidriv 1 e 2 Trapano per muratur...

Page 14: ... livello del suolo devono essere osservate le precauzioni di sicurezza adeguate 1 Inserire i due cappucci per viti dello stesso colore in una confezione separata nei fori di fissaggio della Griglia esterna i fori di fissaggio non sono utilizzati sulla griglia esterna 2 Fissare le due fascette metalliche alla griglia esterna posizionandole negli alloggiamenti in confezione separata e incastrandole ...

Page 15: ...udere completamente le alette e impedire qualsiasi riflusso dell aria 4 Tirare il fermo di microventilazione verso di sé fino a che non clicchi in posizione 5 Riposizionare la griglia interna e la serranda anti ritorno assicurandosi che la leva di azionamento sia in posizione completamente abbassata UN ELETTRICISTA QUALIFICATO DEVE EFFETTUARE TUTTE LE OPERAZIONI DI PULIZIA NOTA LA VENTOLA CONTINUE...

Page 16: ...ن الحفر عمليات كافة أثناء العينين واقي ارتداء يجب تحذير الحائط على للتركيب 1 أو الحائط داخل مدفونة كابالت أو أنابيب هناك توجد ال أنه تأكد المياه أو الغاز أو الكهرباء بأعمال خاص بالخارج عوائق 2 الفتح مركز بأن تحقق مسافة على يقع ة 200 من األقل على مم الحائط حافة الثابتة باألسالك للتوصيل مخصص الجهاز هذا مع يتطابق المروحة على الموضح الكهربائي التصنيف أن تأكد الكهربائي التيار و الشكل 9 أرضية يتطلب وال ...

Page 17: ...ية فتحات بحفر قم 5 مطرقة باستخدام المعجون خالل من بالقص قم وإزميل 6 حامل أو بارد إزميل باستخدام الداخلي الحائط خالل من بالقص قم مستقيم خط في القص تجنب الطوب قوالب 7 ً ا ضمان الخارجي الحائط في فتحة بقص وقم الخارج إلى اذهب للمحاذاة 1 في كما البرغين بنزع وذلك الداخلية الشبكة مجموعة بفك قم و الشكل 10 مجموع لتأمين بصندوق الخاصة الداخلية الشبكة ة المروحة تثبيت 2 تثبيت بصندوق الخاصة المروحة لتأمين البرغي...

Page 18: ...ء يعمل الذي المصراع وينغلق 2 غطائي بنزع الخلفي التيار ومصراع الداخلية الشبكة بفك قم الشبكة مجموعة بتأمين الخاصة والبراغي البرغين بصندوق الداخلية و شكل المروحة تركيب 10 ضع الهواء تيار مصراع إلزالة األعلى نحو المصراع مجموعة واسحب األسفل نحو الداخلية الشبكة ح شكل 1 وح 2 3 الوبر من خالية رطبة قماش بقطعة امسحه المحفز لتنظيف الكيميائية والمنظفات القوية المطهرات استخدام تجنب 4 بت قم في بغمرهما الداخلية و...

Page 19: ...This page has been left blank for the addition any notes you may wish to make ...

Page 20: ...erations to your Xpelair product not carried out by Xpelair service personnel or its authorised dealer s Caused by use of any consumables or spare parts for your Xpelair product which are not Xpelair specified Terms and Conditions The Xpelair Warranty is valid for Xpelair from the date of purchase of your Xpelair product from a recognised retailer in the country of purchase and use or the date of ...

Reviews: