OVEN SERVICE PROCEDURES
Check Incoming Pressure:
Loosen screw one (1) full turn counter clockwise (Figure 1)
Connect Manometer to this test port
Turn the LUI to on position and wait for burner to light (up to 30 seconds)
Document incoming pressure on startup checklist. (If new installation)
Disconnect Manometer
Tighten screw clockwise until snug (Figure 2)
On-Off Valve Adjustment Procedure
Figure 1
Figure 2
Natural Gas
LP Gas
W/C
mbar
kPa
W/C
mbar
kPa
kPa
kPa
W/C mbar kPa W/C mbar kPa
All
6-14
15-35
1.50-3.50
11.5-14 27.5-35
2.75-3.50
1.50-2.50
2.30-3.30
3.5
8.75 0.875 10
25
2.5
Oven
Models
Inlet Pressure Range
LP Gas
Standard, World, Australia and New Zealand
Korea
Gas Oven Fuel Pressure Requirements
Natural Gas
Natural Gas
LP Gas
Manifold Pressure