V5 series inverter
41
P3.01
Parameter initialization
locking up
Unit’s place
:
0: All parameters are allowed
modifying
1: Only P3.01 can be modified
2:Only P0.02 and P3.01 can be
modified
Ten’s place
:
0
:
disabled
1
:
Restore to factory setting
2
:
Clear fault record
1
00
×
P3.02
Parameter copy
0:disabled
1:parameter upload
2:parameter download
Note:Function is still in developing
1
0
×
P3.03
Auto
energy-saving
function
0
:
disabled
1
:
Enabled
1
0
×
P3.04
AVR function
0
:
disabled
1
:
enable all the time
2
:
Disabled in Dec process
1
0
×
P3.05
Gain
of
slip
compensation
0
~
150
%
1
%
0
%
×
P3.06
Jog operating frequency
0.10
~
50.00Hz
0.01Hz
5.00Hz
○
P3.07
Acc time of jog operation
0.1
~
60.0s
0.1s
5.0s
○
P3.08
Dec time of jog operation
0.1
~
60.0s
0.1s
5.0s
○
P3.09
Communication
config
LED unit’s place
:
baud rate selection
0
:
1200BPS
1
:
2400BPS
2
:
4800BPS
3
:
9600BPS
4
:
19200BPS
5
:
38400BPS
LED ten’s place
:
data format
0
:
1
-
7
-
2 foramt
,
no parity check
1
:
1
-
7
-
1 format
,
Odd
2
:
1
-
7
-
1 format
,
Even
3
:
1
-
8
-
2 format
,
None
4
:
1
-
8
-
1 format
,
Odd
5
:
1
-
8
-
1 format
,
Even
6
:
1
-
8
-
1 format
,
None
(When
use
Modbus-RTU
communication mode
,
please select
data mode 3
~
6
。
)
LED hundred’s place:
undefined
1
054
×
P3.10
Local address
0
~
248
0
:
broadcast address
248
:
inverter as the host address
1
1
×
P3.11
Delay for responding to c
0.0
~
1000.0s
0.1s
0.0s
×