Electrical Power Connections
Installations must follow these codes:
•
National Electrical Code and any other national,
state, provincial or local codes or regulations hav-
ing jurisdiction.
•
Safety wiring must be NEC Class 1.
•
Heater must be electrically grounded as required
by the NEC.
•
In Canada, CSA C22. 1 C.E.C. Part 1.
The XFyre 300A–850A heaters are wired for 120 VAC
single-phase 60 Hz power. Consult the wiring diagram
shipped with the heater. Before starting the heater,
check to ensure proper voltage to the heater and
pump(s). A larger circuit breaker may be needed for
pumps larger than 1/4 hp.
The boiler pump (up to 1 hp) and the indirect DHW
pump (up to ¼ hp) get their power supply directly from
the heater power supply (connections are located in
the rear wiring box). The system pump relay is rated
Natural Gas – 1,000 BTU/ft
3
, 0.60 specific gravity at 0.5 in. WC pressure drop
Propane Gas – 2,500 BTU/ft
3
, 1.53 specific gravity at 0.6 in. WC pressure drop
Table K: Maximum Equivalent Pipe Length
Model
No.
3/4” NPT
1” NPT
1-1/4” NPT
1-1/2” NPT
2” NPT
N
P
N
P
N
P
N
P
N
P
300A
15
30
45
100
175
400
390
400A
30
70
120
275
270
414
500A
15
40
65
150
150
350
700A
42
96
96
220
310
795
850A
25
55
55
125
175
450
for pilot duty only. XFyre heaters may power up to 2
pumps directly. Install a circuit breaker sized sufficient-
ly for both the heater and the pump(s). An indirect
DHW pump larger than ¼ hp or 5A must use a sepa-
rate power supply and run the power through an
external field supplied pump contactor. Use appropri-
ately-sized wire as defined by NEC, CSA and/or local
codes. All primary wiring should be 125% of minimum
rating. The indirect and system pumps outputs are
fuse protected.
If any of the original wire as supplied with the heater
must be replaced, it must be replaced with 105°C wire
or its equivalent.
All 120VAC field wiring connections to the XFyre
heater are made inside the rear wiring box as shown
in Fig. 12. Low voltage wiring is connected to the
VERSA control board and the Platform Ignition Module
(PIM) at the front of the unit. Sensors, enable/disable
contacts, (optional) 0-10VDC control wiring, and cas-
cade connections are wired into the VERSA and PIM
field wiring plugs. See the wiring diagram on page 44.
19
Heater
Model No.
STANDARD PUMP MODELS
H7 - Boiler
WH7 - Water Heater
Pump Model
HP
Amps
Pump Model
HP
Amps
300A
0012
1/8
1.3
1611
1/4
5.7
400A
0012
1/8
1.3
1630
1/2
6.9
500A
1611
1/4
5.7
1630
1/2
6.9
700A
1630
1/2
6.9
1634
1
14
850A
1630
1/2
6.9
1634
1
14
Table L: Standard Pump Sizes and Amperages