Installation
10
975-0126-01-01
the same way that the neutral conductor from the utility is tied to ground. These
same codes specify that the neutral can only be connected to ground in one place
at any one time.
Suitability
This automatic neutral-to-ground bonding system is suited for installations in
which the AC input source is known to have a bonded neutral. This will be the
case in most situations: in a utility feed, at an external AC hook-up, or a generator
with a bonded neutral. If not, have an electrician look into bonding the source’s
neutral to ground. See also “AC Input and Output Isolation” on page 21.