Installation
34
975-0126-01-01
Step 7: Performing Checks Prior to Initial Start-Up
Before testing your installation, ensure these conditions are met:
❐
Chassis and AC grounds are properly installed.
❐
AC input connections and AC output connections are wired correctly on the
terminal block and not reversed.
❐
Positive (+) battery cable is connected to the positive (+) battery terminal
through the DC fuse and disconnect switch or DC circuit breaker.
❐
Negative (–) battery cable is connected to the negative (–) battery terminal.
❐
Battery voltage is within the proper range for this unit
(10.3–15.3 volts DC).
❐
DC disconnect switch or breaker is turned off.
❐
AC input and output breakers are turned off.
❐
All connections are tight.