18 TD_PCM1x_Packages_Function/Operation_08.04_GB
3.1.3
Second Display Line
NOTE
The second line can be scrolled using the "STATUS / ALARM" push-button. It is also possible, to scroll through any
alarms that may be present using the "STATUS / ALARM" push-button.
These display screens are displayed in succession by pressing the "STATUS / ALARM" push-button. When the
last display screen has been reached, the basic screen is displayed. If alarms have occurred, their message
texts are displayed in the sequence of their occurrence in the display screens before the basic screen. If item
functions are active (e. g. synchronization of the GCB), the basic screen is superimposed with the correspond-
ing message (e. g. " synchronization"). Following the termination of the item function, the basic screen is dis-
played again.
------------------------
xxxxxxxxxxxxx
Display in automatic mode, second line: measuring value
Instead of
"xxxxxxxxxx"
the following measuring values are displayed:
the maximum generator current (slave pointer),
the four alarm messages which occurred first,
the time/the date (
P01
)
the energy counter kWh.
Succession
Display
Description
0
(Basic display)
--- --- --- --- --- --- --- --
Gen 0,00 0000kW
Generator power factor
ϕ
,
Generator actual real power
1
--- --- --- --- --- --- --- --
max. Gen.strom
Slave pointer (maximum generator current)
2
--- --- --- --- --- --- --- --
Uhrzeit
Time (
Package P01
)
3
(Pickup = ON)
--- --- --- --- --- --- --- --
Gen. 0000U/min
Engine speed (Pickup is activated)
4.1
(alternative to 4.2/4.3)
--- --- --- --- --- --- --- --
P (Netz) 0000kW
Mains actual real power (measured)
4.2
(alternative to 4.1/4.3)
--- --- --- --- --- --- --- --
NT 0,00 +0000kW
Mains power factor
ϕ
Mains actual real power (calculated; + = Export, - = Import)
4.3
(alternative to 4.1/4.2)
--- --- --- --- --- --- --- --
NT LS4: 00000kW
Mains actual real power (measured by PCN4 ;
PCM1-G-..-P01
)
5
--- --- --- --- --- --- --- --
Netzstrom: 0000 A
Mains current (measured)
6.1
(alternativ zu 6.2)
--- --- --- --- --- --- --- --
Netzspg.: 0000 V
Mains voltage (measured)
6.2
(alternativ zu 6.1)
--- --- --- --- --- --- --- --
Netz-Entk: 0000 V
Mains voltage after the mains decoupling (measured by
PCN4;
PCM1-G-..-P01
)