4.2.3 Alarm
Messages
NOTE
The alarm messages can be scrolled in the second line using the "STATUS / ALARM" push-button.
------------------------
yyyyyyyyyyyyyyy
Display in automatic mode, second line: Alarms
If alarms occur, the corresponding alarm messages are displayed in the lower line of the
LC display according to the following list:
Type of alarm
Alarm-
class
Alarm text
Relay output (Terminal)
Engine overspeed (Pickup)
F3
Over speed
Generator overfrequency
F3
Over frequency
Generator underfrequency
F3
Low frequency
Generator overvoltage
F3
Gen.overvolt.
Generator undervoltage
F3
Gen.undervolt.
Generator overcurrent level 1
F3
Gen.overcurr. 1
Generator overcurrent level 2
F3
Gen.overcurr. 2
Reverse/reduced load
F3
Revers/min.power
Overload F2
Gen.overload
Load imbalance
F3
Asymmetric load
Mains overvoltage
F0
Mains-overvolt
Mains undervoltage
F0
Mains-undervolt.
Mains overfrequency
F0
Mains-overfreq.
Mains underfrequency
F0
Mains-underfreq.
Mains phase shift
F0
Vectorjump
Battery undervoltage
F1
Batt.undervolt.
GCB synchronization time monitoring (syn.)
F1
GCB syn.failure
MCB synchronization time monitoring (syn.)
F1
MCB syn.failure
Switching to black busbar time monitoring
F1
Failure df/dVmax.
Mechanical GCB malfunction on closing
F1
GCB close failure
Mechanical MCB malfunction on closing
F1
MCB close failure
Mechanical GCB malfunction on opening
F1
GCB open failure
Mechanical MCB malfunction on opening
F1
MCB open failure
Faulty ref. power zero control with interch. syn. GCB
F1
Power not zero
Maintenance call
F1
Service
Interface monitoring X1..X5
F1
Interf.err.X1X5
Interface monitoring Y1..Y5
F1
Interf.err.Y1Y5
Plausibility control Pickup/generator frequency
F3
Pickup/Gen.freq.
Shutoff malfunction
F3
Stop failure
Start failure
F3
Startfail
Unintended stop
F3
Not wanted stop
Add-on time GCB (asyn.)
F1
GCB syn.failure
Add-on time MCB (asyn.)
F1
MCB syn.failure
[PCM1-G] Fault mains decoupling with rel. 39/40
F1
EXT open failure
P rRamp GCB on failure add/stop time
F1
P-rampe: open GCB
Description
in chapter "Alarm"
on page 28
Group alarm
via the
Relay manager
with the
parameter 85
Table 4.4: Alarms – Text messages