TD_PCM1x_Packages_Function/Operation_08.04_GB 23
GB
Aux.serv.prerun
D
Vorl.Hilfsbetr.
Operating mode: Auxiliary operation Pre-run
Before each starting procedure (except of an emergency operation) one of the re-
lays keeps picked up as long as this message is monitored. With it external instal-
lations can be prepared on the engine start (e.g. open sunblind, start cooling wa-
ter pumps etc.).
GB
Aux.serv.postrun
D
Nachl.Hilfsbetr.
Operating mode: Auxiliary operation Coasting
After the engine stops one of the relays keeps picked up, until this message ex-
pires. With it e.g. hot cooling water will be pumped out of the engine and will be
still cooled down after the stop.
GB
Start-Pause
D
Start-Pause
Operating mode: Pause between two start attempts
An interrupted starting process is displayed.
GB
Testmode
D
Probebetrieb
Operating mode: TEST
The operating mode TEST is selected and the display appears alternately with the
currently carried out action.
GB
Load test
D
Lastprobebetrieb
Operating mode: Load test
In operating mode TEST, load test is carried out after the button "GCB ON" was
operated.
GB
Emergency run
D
Notstrom
Operating mode: Emergency
Emergency power was identified and carried out.
GB
Mains settl.000s
D
Netzber. 000s
Operating mode: Mains settling time
The displayed message shows the mains settling time following a mains failure.
There is shown the remaining mains setting time.
GB
Sprinkler
D
Sprinklerbetrieb
Operating mode: Sprinkler operation
Sprinkler operation is carried out.
GB
Sprinkler shutd.
D
Sprinkler Nachl.
Operating mode: Sprinkler coasting
Following sprinkler operation, the engine operates without load for 10 minutes.
This message is shown in the display during this period.
GB
Cool down 000s
D
Nachlauf 000s
Operating mode: Engine coasting
No-load operation (engine cooling) prior to engine shutdown is displayed with this
message. There is also shown the remaining coasting time.
GB
Stop engine!
D
Motor Stop!
Operating mode: Engine stop!
When stopping the engine, a starting block is set for 10 seconds on negative de-
viation from the firing speed. This message displays the operating condition.
GB
Unloading
D
Leistungsred.
Operating mode: Power reduction
Power reduction is carried out. For this reason the generator power is reduced via
a linear ramp.