Manual 26694
2301E-ST
Woodward
73
02 LINK ERROR
indicates Link Error sets TRUE when the slave fails to answer a data request in
specified number of time-out seconds.
03 ERROR PERCENT
Error Percent outputs reflects communication quality as a percentage by dividing the number of exception
errors detected by the total number of communication transactions. This essentially gives the number of
message/packet errors detected.
04 ERROR NUMBER
Error Number outputs the code number of the communication/exception error that occurred.
Table 3-3. Communication Error Code
CODE NAME
MEANING
00
NO ERROR
Error free
The following are returned to the master.
01 ILLEGAL
FUNCTION
Message function received is not an allowable action for addressed slave.
(Unsupported or illegal function code).
02 ILLEGAL
DATA
ADDRESS
Address referenced in data field is not an allowable address for the
addressed slave location. (Master requested data, which is not configured
from slave).
03 ILLEGAL
DATA
VALUE
Amount of data requested from slave was too large for slave to return in a
single response. Woodward maximum is 118 registers.
The following are displayed only.
09 CHECKSUM
ERROR
Error in the checksum. Can indicate link quality and/or noise problems.
10 GARBLED
MESSAGE
Data received by the slave, but it is too short to be a valid Modbus
message/command.
05 BAUD RATE
dflt=10 (7, 12)
Set the Baud rate, which defines the transfer rate for port communications.
8=9600
9=19200 10=38400
11=57600 12=115200
06 BAUD RATE IS SET FOR
Shows the selected Baud rate.
07 DATA BITS
dflt=2 (1, 2)
Set the Data bits input defines the protocol for the number of data bits in the data packets.
1=7
2=8
08 DATA BITS ARE SET FOR
Shows the selected data bits.
09 STOP BITS
dflt=1 (1, 3)
Set the Stop bits, which defines the number of stop bits for the communications protocol. Stop bits specify
the time that elapses between transmitted characters.
1=1 stop bit
2=2 stop bits
3=1.5 stop bits
10 STOP BITS ARE SET FOR
Shows the selected stop bits setting.
11 PARITY
dflt=1 (1, 3)
Set the Parity input defines protocol for the parity. If you selected 8 data bits select '1' for none.
1=OFF (none)
Released
Summary of Contents for 2301E-ST
Page 15: ...Manual 26694 2301E ST Woodward 13 Figure 2 1a 2301E ST Outline Drawing 8273 1013 1014 Released...
Page 17: ...Manual 26694 2301E ST Woodward 15 Figure 2 2a 2301E ST Plant Wiring Diagram sheet 1 Released...
Page 18: ...Manual 26694 2301E ST Woodward 16 Figure 2 2b 2301E ST Plant Wiring Diagram sheet 2 Released...
Page 19: ...Manual 26694 2301E ST Woodward 17 Figure 2 2c 2301E ST Plant Wiring Diagram notes Released...
Page 125: ...Manual 26694 2301E ST Woodward 123 Declarations Released...