Manual 26694
2301E-ST
Woodward
67
03 RELAY 1 LEVEL SELECT FOR
displays the level function selected for terminal 44.
04 RELAY 1 ON LEVEL
dflt=0.0 (-32000.0, 32000.0)
Enter the level switch ON setting in engineering units. There is an ON and an OFF setting for each level
switch option. This allows the user to program the desired hysteresis for the function selected.
05 RELAY 1 OFF LEVEL
dflt=0.0 (-32000.0, 32000.0)
Enter the level switch OFF setting in engineering units.
(Must be less than the ‘Relay On Level’)
06 RELAY 2 SELECTED AS
displays the function selected for terminal 45. This relay is selected in the
configure menu - C**DISCRETE OUT OPTIONS**
07 RELAY 2 LEVEL SW (1-7)
dflt=1 (1, 7)
Select one of the following parameters for discrete output at terminals 45 when it was selected as a level
switch.
1=NOT USED
2=ACTUAL SPEED
3=SPEED SETPOINT
4=VALVE LIMITER SETPOINT
5=ACTUATOR DEMAND
6=GENERATOR OUTPUT (LOAD SENSOR)
7=MONITOR SIGNAL
08 RELAY 2 LEVEL SELECT FOR
displays the level function selected for terminal 45.
09 RELAY 2 ON LEVEL
dflt=0.0 (-32000.0, 32000.0)
Enter the level switch ON setting in engineering units. There is an ON and an OFF setting for each level
switch option. This allows the user to program the desired hysteresis for the function selected.
10 RELAY 2 OFF LEVEL
dflt=0.0 (-32000.0, 32000.0)
Enter the level switch OFF setting in engineering units.
(Must be less than the ‘Relay On Level’).
11 RELAY 3 SELECTED AS
displays the function selected for terminal 46. This relay is selected in the
configure menu - C**DISCRETE OUT OPTIONS**
12 RELAY 3 LEVEL SW (1-7)
dflt=1 (1, 7)
Select one of the following parameters for discrete output at terminals 46 when it was selected as a level
switch.
1=NOT USED
2=ACTUAL SPEED
3=SPEED SETPOINT
4=VALVE LIMITER SETPOINT
5=ACTUATOR DEMAND
6=GENERATOR OUTPUT (LOAD SENSOR)
7=MONITOR SIGNAL
13 RELAY 3 LEVEL SELECT FOR
displays the level function selected for terminal 46.
14 RELAY 3 ON LEVEL
dflt=0.0 (-32000.0, 32000.0)
Enter the level switch ON setting in engineering units. There is an ON and an OFF setting for each level
switch option. This allows the user to program the desired hysteresis for the function selected.
15 RELAY 3 OFF LEVEL
dflt=0.0 (-32000.0, 32000.0)
Enter the level switch OFF setting in engineering units.
(Must be less than the ‘Relay On Level’)
Released
Summary of Contents for 2301E-ST
Page 15: ...Manual 26694 2301E ST Woodward 13 Figure 2 1a 2301E ST Outline Drawing 8273 1013 1014 Released...
Page 17: ...Manual 26694 2301E ST Woodward 15 Figure 2 2a 2301E ST Plant Wiring Diagram sheet 1 Released...
Page 18: ...Manual 26694 2301E ST Woodward 16 Figure 2 2b 2301E ST Plant Wiring Diagram sheet 2 Released...
Page 19: ...Manual 26694 2301E ST Woodward 17 Figure 2 2c 2301E ST Plant Wiring Diagram notes Released...
Page 125: ...Manual 26694 2301E ST Woodward 123 Declarations Released...