To download the settings file, Open Control Assistant software and connect. Put the control into I/O lock
by selecting the Lock I/O icon
. This will cause an I/O lock and could shutdown the engine. BE
CAREFUL! Answer Yes to Locking I/O question. Open the saved .tc settings file. Select the “Send
Tunable List (IO Lock Required) icon
. The settings file will be sent to the control.
Tuning a parameter, a popup appears:
Standard password: 1112 for full editing mode.
Tuning a parameter is possible, by typing or using the up and down arrows. The first arrow is a change of
1% and the other makes a change of 10%. During operation no larger change than 10% possible.
After tuning a parameter it is immediately used by the control, but still needs to be saved into non- volatile
memory.