B** DISPLAY LOAD INFO **
Figure 3-10. Service: B** DISPLAY LOAD INFO ** Menu
This menu is used for general monitoring of the generator information.
01 LOAD CONTROL STATUS
displays generator load control mode. Will display one of the following:
NO LOAD CONTROL
KW DROOP
SPEED DROOP
ISOCHRONOUS
UNLOADING
LOADING
02 LOAD SENSOR INPUT (KW)
displays generator load in kilowatt. This value is calculated as the
current (I) multiplied by the phase angle between the voltage (V) and the current (I), (cos theta).
03 LOAD SENSOR PERCENTAGE
displays the generator load in percentage (0-100%).
04 LOAD SHARING BIAS (RPM)
displays the speed bias, in rpm, from the load sharing input.
05 LOAD SIGNAL OUT (VDC)
indicates the generator KW in units of load Gain voltage. The value will
vary from 0.0 to 6.0 Vdc as the generator load varies from 0 to rated KW.
06 SYSTEM LOAD 0-3 (Vdc)
displays the system load on the load sharing line as a function of the load
sharing lines. 0 equals zero percent load, 3 equals 100 percent load.
07 LOAD SHARING BIAS
displays the speed bias percentage (0-100%).
Released
Summary of Contents for 2301E-ST
Page 15: ...Manual 26694 2301E ST Woodward 13 Figure 2 1a 2301E ST Outline Drawing 8273 1013 1014 Released...
Page 17: ...Manual 26694 2301E ST Woodward 15 Figure 2 2a 2301E ST Plant Wiring Diagram sheet 1 Released...
Page 18: ...Manual 26694 2301E ST Woodward 16 Figure 2 2b 2301E ST Plant Wiring Diagram sheet 2 Released...
Page 19: ...Manual 26694 2301E ST Woodward 17 Figure 2 2c 2301E ST Plant Wiring Diagram notes Released...
Page 125: ...Manual 26694 2301E ST Woodward 123 Declarations Released...