Any of the four relays can be programmed to function as a level switch. When programmed as a level
switch the relay will change state when the selected parameter reaches the programmed level (energizes
when value is higher the programmed level). The following is a list of the level switches:
TURBINE
SPEED
TURBINE SPEED REFERENCE
VALVE LIMITER REFERENCE
ACTUATOR
DEMAND
GENERATOR
OUTPUT
SIGNAL
MONITOR
These discrete outputs are low-side drivers with a maximum output current of 160 mA. The discrete
output drivers are isolated from the control’s internal power supply, but not from each other and are
powered by an ex12 Vdc or +24 Vdc source connected at terminals 42(+) and 43(–). Refer to
Figure 2-2 for plant wiring information.
Relay Driver Clarifications
1. SHUTDOWN
Each relay driver can be programmed to indicate a Shutdown Condition (energizes for a shutdown
condition) or a Trip Relay (de-energizes for a shutdown/trip).
2. ALARM
Each relay driver can be programmed to indicate a general Alarm Condition (energizes for an alarm
condition) or an Alarm Relay (de-energizes for an alarm).
3. ELECTRICAL OVERSPEED TEST
Each relay driver can be programmed to indicate that the electrical turbine overspeed was sensed.
4. VALVE LIMITER IN CONTROL
Each relay driver can be programmed to indicate the valve limiter controls the actuator/ valve.
5. SPEED PID IN CONTROL
Each relay driver can programmed to indicate the speed PID controls the actuator/valve.
6. MODBUS CONTROLLED RELAY #1
Each relay driver can be programmed to indicate the Modbus controlled relay #1 according to the
following function.
7. MODBUS CONTROLLED RELAY #2
Each relay driver can be programmed to indicate the Modbus controlled relay #2 according to the
following function.
8. MODBUS CONTROLLED RELAY #3
Each relay driver can be programmed to indicate the Modbus controlled relay #3 according to the
following function.
9. MODBUS CONTROLLED RELAY #4
Each relay driver can be programmed to indicate the Modbus controlled relay #4 according to the
following function.
10. LEVEL SWITCH
Each relay driver can be programmed to function as a level switch. If the level switch feature is
selected, its ON level and OFF level must also be configured.
Released
Summary of Contents for 2301E-ST
Page 15: ...Manual 26694 2301E ST Woodward 13 Figure 2 1a 2301E ST Outline Drawing 8273 1013 1014 Released...
Page 17: ...Manual 26694 2301E ST Woodward 15 Figure 2 2a 2301E ST Plant Wiring Diagram sheet 1 Released...
Page 18: ...Manual 26694 2301E ST Woodward 16 Figure 2 2b 2301E ST Plant Wiring Diagram sheet 2 Released...
Page 19: ...Manual 26694 2301E ST Woodward 17 Figure 2 2c 2301E ST Plant Wiring Diagram notes Released...
Page 125: ...Manual 26694 2301E ST Woodward 123 Declarations Released...