W5500S2E-S1 serial to Ethernet module
W5500S2E-S1 user manual
12
Figure 4-2 WIZS2E ConfigTool search result
4.3
Module and host computer network detection
Before starting to communicate between the WIZS2E module and the host computer, please ensure
the host computer and the module are in the same network segment.
The factory default setting for IP address and Subnet mask in WIZS2E module are 192.168.1.88 and
255.255.255.0 respectively. User could follow the flow diagram 4-3 to understand the
communication procedure between the module and the host computer. If they are in the same
network segment, it could communicate with the module. Otherwise, the host computer needs to
change its IP address to communicate with the module.
W5500S2E-S1 IP Address
192.168.1.88
and
W5500S2E-S1 Submask
255.255.255.0
PC Submask
?
and
PC IP Address
?
W5500S2E-S1 Subnet
192.168.1.0
PC Subnet
?
Compare
Use W5500S2E-S1 to Communicate
Change IP Address
Different Subnet
The Same Subnet
Figure 4-3 WIZS2E module and IP segment of host computer flow diagram