Option: Ventilation time module (time ventilation module WSA 303)

 

Automatic closing in the ventilation mode according to pre selected time (1 min. to 30 min.) after ventilation 
OPEN or STOP was actuated 

Once this time has elapsed, the actuators close after ventilation „OPEN“ or 

ventilation „STOP“. This function is not operative if the setting potentiometer is on the right-hand stop.   
 

Option: Gab ventilation module (module WSA 304B) WSC 204 / WSC 204KP /  
WSC 204MH 

It is not always necessary for an electric actuator to open a ventilation unit (window or light dome) by its full 
stroke. Sometimes, a small gap is sufficient for ventilation purposes. This module enables time-controlled 
limitation of the actuator stroke (the opening time can on the potentiometer be set from 1 - 60 sec). Even re-
triggered in ”OPEN” direction the window will not open further than set preset opening value 

 

The module has no influence on the actuator when an ”EMERGENCY OPEN” function is triggered. In this case 
the actuator opens to its maximum stroke. 
 
It is 

not

 possible to install both a WSA 303 and a WSA 304B module in one smoke control panel. 

 

Wind/rain CLOSE 

The actuators close when the wind/rain sensor has been activated (potential free contact in the sensor 
switches).  
As long as the sensor is activated, the ventilation function is out of operation and the green wind/rain LED 
lights. 

Activated alarm has 1. priority. 
 

Option: Transmission of the wind/rain signal (module WSA 302)

 

The activated signal of the wind/rain sensor can be transmitted potential free to the next smoke control panel. 

 

1 x change-over contact (max. load: 60V, 1A) with 3 pole connection terminal for potential free transmission 
of the wind/rain trip. 
 

CLOSE after a power failure 

2 minutes after a power failure actuators opened for natural ventilation will automatically close. 
In the event of alarm, this function will be out of operation. 

 

4.3.  General information 

 

EMC protection 

All inputs and outputs are protected from coupled in electrical interferences. 

 

Short-circuit protection 

All outputs are protected against short-circuit and overload. 

 

4.4.  Connection possibilities 

1)  Actuators with a total power consumption of max. 4A 
2)  Smoke detectors, up to 10 pieces in 1 sensor group 
 

Optical smoke detector and/or thermo-differential sensor  

 

and/or heat max. sensor 

 

 

 

 

WSA 300, WSA 310 

3)  Break glass units (main), up to 4 per sensor group   

WSK 320 000X* 

4)  Break glass units (secondary), up to 15 

 

 

WSK 330 000X 

5) 

Ventilation buttons with ‘indicator, up to 15,  

 

any number without ‘open’ indicator  

 

 

WSK 100 1161 

6)  Wind/rain detector with potential free close contact   

WLA 330 01, WLA 331 01 

7)  SHE activation on potential free 

ASV contact in the smoke detector connector 

 

WSA 306 to be installed 

 
* incl. the break glass unit in the door on the WSC 204KP 

 

Summary of Contents for WSC 204

Page 1: ...04BZ 0102 WSC 204KP 0102 install 1606 UK WindowMaster 2011 2016 WindowMaster is a registered trademark used under licence by WindowMaster Group WSC 204 WSC 204 0102 WSC 204MH 0102 WSC 204KP 0102 WSC 2...

Page 2: ...10 4 6 Back up batteries charge 10 4 7 Operation Setting possibilities 10 5 Installation 11 5 1 Surface mounting 11 5 2 Countersunk mounting 12 5 3 Cable routing 12 5 4 Installation 12 5 5 Installatio...

Page 3: ...ause death severe injury or considerable damage to assets The connection of the control system is reserved for qualified personnel Disconnect all poles of the unit from the supply voltage prior to ope...

Page 4: ...batteries are fully charged 1 9Ah Current load of the actuators battery and 230V operation max 4 8A Current load of the smoke unit batteries surveillance periphery max 0 7A Switch on duration 40 ED Re...

Page 5: ...ights to make changes 2 1 Accessories Alarm and fault module master slave WSA 301 Linking of wind rain signal module WSA 302 Timer ventilation module WSA 303 Gap ventilation module WSA 304B ASV Module...

Page 6: ...6 3 Operating elements and fuse review...

Page 7: ...ators The first 30 min after a SHE trig on WSC 204BZ only when triggered the break glass unit the actuators will be cyclically activated every 2 min in OPEN direction to loosen frost fastened windows...

Page 8: ...on is only displayed in the corresponding smoke control panel and in the break glass unit connected to the master smoke control panel primary break glass unit type WSK 320 Option ASV connection module...

Page 9: ...entilation function is out of operation and the green wind rain LED lights Activated alarm has 1 priority Option Transmission of the wind rain signal module WSA 302 The activated signal of the wind ra...

Page 10: ...ossible Preset To show the activation the LED will flash 10 sec If SW1 1 is once again set on OFF during these 10 sec the prioritised activation is cancelled After a period of 12 month the inspection...

Page 11: ...f Flashes when interrupted Lits when short circuit Check wiring and jumper J1 in the last or only break glass unit Rauchmelder smoke detector yellow Off Flashes when interrupted Lits when short circui...

Page 12: ...E30 See also Cable Length page 12 However this has to be agreed with the Engineer or if necessary with the local fire protection department Do not reduce the cable cross sections specified in the cabl...

Page 13: ...bles cross sections please refer to the following table Maximum actuator current 4 8A Note Be aware of the overall capacity of the smoke control panel Actuating current Sum of all motor currents per g...

Page 14: ...14 7 Cable plan Smoke control panel WSC 204 204MH 204BZ 204KP With back up batteries Mains 230VAC 50 60Hz 150W...

Page 15: ...15 8 Wiring diagram 8 1 Standard wiring diagram...

Page 16: ...16 8 2 Wiring diagram WSC 204KP...

Page 17: ...17 8 3 Various wiring diagrams...

Page 18: ...accumulator LED is OFF The malfunction message at the operating panels is OFF 4 Ventilation keypad Closely observe the actuators during opening and closing They must not be impaired in any position by...

Page 19: ...they will automatically close after 2 minutes e Test the SHE trip and reset closed as described under 5 f Refit the mains fuse g The green mains and operating LED s are ON the yellow accumulator LED i...

Page 20: ...in the smoke panel and the break glass unit Remove all soiling from the units of the smoke and heat extraction system Check fastening and clamping screws for firm seating Carry out a test run of the...

Reviews: