2. Technical description
Function
WSC 204 / WSC 204KP / WSC 204MH
Opens
the window actuators when triggered by a SHE-signal caused by smoke
detector or break glass unit.
WSC 204BZ
Closes
the window actuators when triggered by a SHE-signal caused by smoke
detector and opens the actuators when activating a break glass unit.
Supply voltage
230V AC / 50/60Hz ((±10%))
Safety transformer
according EN 61558
Power consumption
max. 150VA
Actuator secondary voltage
rated voltage 24V
open circuit voltage at 230 VAC typ. 28V DC
open circuit voltage at 253VAC max 31.3V DC
actuator voltage at 230 VAC / 4.8A load typ. 22V DC
ripple at full load (4.8A) max. 6% (= 3.8Vpp)
open circuit voltage at battery operation min 18.7V DC
Inrush current
Max 6A<5msec
Standby consumption
4W
Switch time between 230V- and
battery operation
max 2.5sec
Emergency power supply
batteries
2 x 12V / 3,4Ah. Expected lifetime 4 years. (2pcs. WSA 003). Only use genuine
WindowMaster back up batteries.
Charging unit:
Charging voltage: 27,7
– 27,8 at 20ºC
Charging current: 350mA, current limited
Operating duration (emergency
power supply )
72 hours if batteries are fully charged (1,9Ah)
Current load of the actuators
(battery and 230V operation)
max. 4,8A
Current load of the smoke unit
(batteries, surveillance, periphery)
max. 0,7A
Switch-on duration
40% ED
Reopening the actuators
during the first 30 min. after a SHE-trig the actuators cyclically every 2 min.
Review of fuses
mains 1A slow-blow
actuator fuse 5A slow-blow
battery 630mA medium slow-blow
Type of connection to external
mains screw terminal / plug-screw terminals / 0.5-2.5mm²
Cable monitoring
automatic detectors (detector circuit with active end module), break glass unit
(detector circuit with end resistor), actuators (with motor end module), batteries
(cyclic measurement)
Message OK, fault and alarm
optically alternating or steady signals by LED's:
steady green LED = operating
alternating yellow LED = malfunction of battery(at battery voltage less than 19V
or above 29V), actuator, break glass unit or smoke
steady red LED = alarm (short circuit)
Automatic smoke triggering
Smoke triggering when temperature inside the compact unit exceeds 72°C
Operating conditions
-5°C - 40°C, max. 90% relative humidity (not condensing)
Approval / Certification
WSC 204 / WSC 204KP / WSC 204BZ: approved according to EN12101-10
Protection type
WSC 204 / WSC 204KP / WSC 204BZ
IP 30 (plastic housing)
WSC 204MH
IP54 (steel housing)