2. Technical description 

 

Function 

WSC 204 / WSC 204KP / WSC 204MH 

Opens

 the window actuators when triggered by a SHE-signal caused by smoke 

detector or break glass unit.  
 
WSC 204BZ 

Closes

 the window actuators when triggered by a SHE-signal caused by smoke 

detector and opens the actuators when activating a break glass unit. 

Supply voltage 

230V AC / 50/60Hz ((±10%)) 

Safety transformer 

according EN 61558 

Power consumption 

max. 150VA 

Actuator secondary voltage 

rated voltage                                                       24V 
open circuit voltage at 230 VAC                         typ. 28V DC 
open circuit voltage at 253VAC                          max 31.3V DC 
actuator voltage at 230 VAC / 4.8A load             typ. 22V DC 
ripple at full load (4.8A)                                       max. 6% (= 3.8Vpp) 
open circuit voltage at battery operation             min 18.7V DC 

Inrush current 

Max 6A<5msec 

Standby consumption 

4W 

Switch time between 230V- and 
battery operation 

max 2.5sec 

Emergency power supply 
batteries 

2 x 12V / 3,4Ah. Expected lifetime 4 years. (2pcs. WSA 003). Only use genuine 
WindowMaster back up batteries. 

Charging unit: 

Charging voltage: 27,7 

– 27,8 at 20ºC 

Charging current: 350mA, current limited 

Operating duration (emergency 
power supply ) 

72 hours if batteries are fully charged (1,9Ah) 

Current load of the actuators 
(battery and 230V operation) 

max. 4,8A  

Current load of the smoke unit  
(batteries, surveillance, periphery) 

max. 0,7A 

Switch-on duration 

40% ED 

Reopening the actuators 

during the first 30 min. after a SHE-trig the actuators cyclically every 2 min. 

Review of fuses 

mains 1A slow-blow 
actuator fuse 5A slow-blow 
battery 630mA medium slow-blow 

Type of connection to external 

mains screw terminal / plug-screw terminals / 0.5-2.5mm² 

Cable monitoring 

automatic detectors (detector circuit with active end module), break glass unit 
(detector circuit with end resistor), actuators (with motor end module), batteries 
(cyclic measurement) 

Message OK, fault and alarm 

optically alternating or steady signals by LED's: 
steady green LED = operating 
alternating yellow LED = malfunction of battery(at battery voltage less than 19V  
                                       or above 29V), actuator, break glass unit or smoke  
steady red LED = alarm (short circuit) 

Automatic smoke triggering 

Smoke triggering when temperature inside the compact unit exceeds 72°C 

Operating conditions 

-5°C - 40°C, max. 90% relative humidity (not condensing) 

Approval / Certification 

WSC 204 / WSC 204KP / WSC 204BZ: approved according to EN12101-10  

Protection type 

WSC 204 / WSC 204KP / WSC 204BZ 
IP 30 (plastic housing)  
 
WSC 204MH 
IP54 (steel housing) 

Summary of Contents for WSC 204

Page 1: ...04BZ 0102 WSC 204KP 0102 install 1606 UK WindowMaster 2011 2016 WindowMaster is a registered trademark used under licence by WindowMaster Group WSC 204 WSC 204 0102 WSC 204MH 0102 WSC 204KP 0102 WSC 2...

Page 2: ...10 4 6 Back up batteries charge 10 4 7 Operation Setting possibilities 10 5 Installation 11 5 1 Surface mounting 11 5 2 Countersunk mounting 12 5 3 Cable routing 12 5 4 Installation 12 5 5 Installatio...

Page 3: ...ause death severe injury or considerable damage to assets The connection of the control system is reserved for qualified personnel Disconnect all poles of the unit from the supply voltage prior to ope...

Page 4: ...batteries are fully charged 1 9Ah Current load of the actuators battery and 230V operation max 4 8A Current load of the smoke unit batteries surveillance periphery max 0 7A Switch on duration 40 ED Re...

Page 5: ...ights to make changes 2 1 Accessories Alarm and fault module master slave WSA 301 Linking of wind rain signal module WSA 302 Timer ventilation module WSA 303 Gap ventilation module WSA 304B ASV Module...

Page 6: ...6 3 Operating elements and fuse review...

Page 7: ...ators The first 30 min after a SHE trig on WSC 204BZ only when triggered the break glass unit the actuators will be cyclically activated every 2 min in OPEN direction to loosen frost fastened windows...

Page 8: ...on is only displayed in the corresponding smoke control panel and in the break glass unit connected to the master smoke control panel primary break glass unit type WSK 320 Option ASV connection module...

Page 9: ...entilation function is out of operation and the green wind rain LED lights Activated alarm has 1 priority Option Transmission of the wind rain signal module WSA 302 The activated signal of the wind ra...

Page 10: ...ossible Preset To show the activation the LED will flash 10 sec If SW1 1 is once again set on OFF during these 10 sec the prioritised activation is cancelled After a period of 12 month the inspection...

Page 11: ...f Flashes when interrupted Lits when short circuit Check wiring and jumper J1 in the last or only break glass unit Rauchmelder smoke detector yellow Off Flashes when interrupted Lits when short circui...

Page 12: ...E30 See also Cable Length page 12 However this has to be agreed with the Engineer or if necessary with the local fire protection department Do not reduce the cable cross sections specified in the cabl...

Page 13: ...bles cross sections please refer to the following table Maximum actuator current 4 8A Note Be aware of the overall capacity of the smoke control panel Actuating current Sum of all motor currents per g...

Page 14: ...14 7 Cable plan Smoke control panel WSC 204 204MH 204BZ 204KP With back up batteries Mains 230VAC 50 60Hz 150W...

Page 15: ...15 8 Wiring diagram 8 1 Standard wiring diagram...

Page 16: ...16 8 2 Wiring diagram WSC 204KP...

Page 17: ...17 8 3 Various wiring diagrams...

Page 18: ...accumulator LED is OFF The malfunction message at the operating panels is OFF 4 Ventilation keypad Closely observe the actuators during opening and closing They must not be impaired in any position by...

Page 19: ...they will automatically close after 2 minutes e Test the SHE trip and reset closed as described under 5 f Refit the mains fuse g The green mains and operating LED s are ON the yellow accumulator LED i...

Page 20: ...in the smoke panel and the break glass unit Remove all soiling from the units of the smoke and heat extraction system Check fastening and clamping screws for firm seating Carry out a test run of the...

Reviews: