1. Safety information  

Attention! 
Adherence to the following information is mandatory:

 

Only allow correspondingly trained, qualified and skilled personnel to carry out installation work.  
 
Reliable operation and the avoidance of damage and hazards is only guaranteed if installation and settings are 
carried out carefully in accordance with these instructions.  
 
Hazards to persons ensuing from flaps and wings operated by electric motors.  
 
The forces occurring in the automatic mode can be such that parts of the body could get crushed.  
When opened, actuators could protrude into the room. For this reason, measures have to be taken prior to 
starting up the actuators, which exclude the danger of injury.  
 
With wings tilting inwards or outwards, the wing must be protected from hinging down once the actuator is 
unhooked (e.g. for window cleaning).  
For safety reasons we recommend the use of catching shears.  
 
In the event that wings and flaps are subjected to rain or high wind loads, we recommend to connect a rain 
and/or wind detector to the smoke control panel, which will automatically close the flaps when comfort 
ventilation. 
 
The house can be mounted either as counter sunk or surface. 
The manufacturer does not assume any liability for possible damage resulting from inappropriate use.  

 
230V AC  dangerous voltage  

Can cause death, severe injury or considerable damage to assets.  
The connection of the control system is reserved for qualified personnel.  
Disconnect all poles of the unit from the supply voltage prior to opening, installation or assembling. Adhere to 
national regulations. 

 
Field of application  

The central control system is exclusively designed for the automatic closing of smoke extraction systems, 
windows, flaps or doors.  
Always check that your system meets the valid regulations.  
Pay particular attention to the opening cross section, the opening time and opening speed. The cable cross 
sections depend on the cable length and current consumption (amperage).  
 

Maintenance work  

See last page in this instruction. 
 

Cable routing and electrical connection  

Fuse the 230V AC power supply cable separately on site.  
 

Leave the insulation of the power supply cable in place up to the mains terminal.  
 

Adhere to the DIN and VDE regulations (Germany) or equivalent in your country.  
Establish the cable types, if necessary, with the local approval bodies or the fire protection authority.  
Do not conceal flexible cables. Junction box must be accessible for maintenance purposes.  
Disconnect all poles of the mains voltage and the accumulators prior to starting maintenance work or making 
changes to the system.  
Secure the system to prevent unintentional switching on again.  
Design cable types, lengths and cross sections in accordance with the technical information.  
Route all low voltage cables (24V DC) separate from the power current cables.  

 
 

 

Summary of Contents for WSC 204

Page 1: ...04BZ 0102 WSC 204KP 0102 install 1606 UK WindowMaster 2011 2016 WindowMaster is a registered trademark used under licence by WindowMaster Group WSC 204 WSC 204 0102 WSC 204MH 0102 WSC 204KP 0102 WSC 2...

Page 2: ...10 4 6 Back up batteries charge 10 4 7 Operation Setting possibilities 10 5 Installation 11 5 1 Surface mounting 11 5 2 Countersunk mounting 12 5 3 Cable routing 12 5 4 Installation 12 5 5 Installatio...

Page 3: ...ause death severe injury or considerable damage to assets The connection of the control system is reserved for qualified personnel Disconnect all poles of the unit from the supply voltage prior to ope...

Page 4: ...batteries are fully charged 1 9Ah Current load of the actuators battery and 230V operation max 4 8A Current load of the smoke unit batteries surveillance periphery max 0 7A Switch on duration 40 ED Re...

Page 5: ...ights to make changes 2 1 Accessories Alarm and fault module master slave WSA 301 Linking of wind rain signal module WSA 302 Timer ventilation module WSA 303 Gap ventilation module WSA 304B ASV Module...

Page 6: ...6 3 Operating elements and fuse review...

Page 7: ...ators The first 30 min after a SHE trig on WSC 204BZ only when triggered the break glass unit the actuators will be cyclically activated every 2 min in OPEN direction to loosen frost fastened windows...

Page 8: ...on is only displayed in the corresponding smoke control panel and in the break glass unit connected to the master smoke control panel primary break glass unit type WSK 320 Option ASV connection module...

Page 9: ...entilation function is out of operation and the green wind rain LED lights Activated alarm has 1 priority Option Transmission of the wind rain signal module WSA 302 The activated signal of the wind ra...

Page 10: ...ossible Preset To show the activation the LED will flash 10 sec If SW1 1 is once again set on OFF during these 10 sec the prioritised activation is cancelled After a period of 12 month the inspection...

Page 11: ...f Flashes when interrupted Lits when short circuit Check wiring and jumper J1 in the last or only break glass unit Rauchmelder smoke detector yellow Off Flashes when interrupted Lits when short circui...

Page 12: ...E30 See also Cable Length page 12 However this has to be agreed with the Engineer or if necessary with the local fire protection department Do not reduce the cable cross sections specified in the cabl...

Page 13: ...bles cross sections please refer to the following table Maximum actuator current 4 8A Note Be aware of the overall capacity of the smoke control panel Actuating current Sum of all motor currents per g...

Page 14: ...14 7 Cable plan Smoke control panel WSC 204 204MH 204BZ 204KP With back up batteries Mains 230VAC 50 60Hz 150W...

Page 15: ...15 8 Wiring diagram 8 1 Standard wiring diagram...

Page 16: ...16 8 2 Wiring diagram WSC 204KP...

Page 17: ...17 8 3 Various wiring diagrams...

Page 18: ...accumulator LED is OFF The malfunction message at the operating panels is OFF 4 Ventilation keypad Closely observe the actuators during opening and closing They must not be impaired in any position by...

Page 19: ...they will automatically close after 2 minutes e Test the SHE trip and reset closed as described under 5 f Refit the mains fuse g The green mains and operating LED s are ON the yellow accumulator LED i...

Page 20: ...in the smoke panel and the break glass unit Remove all soiling from the units of the smoke and heat extraction system Check fastening and clamping screws for firm seating Carry out a test run of the...