9.  Commisioning and troubleshooting  

When error message occur, please refer to chapter Function description see Operating elements/LED 
diagnosis. 
 
An acoustic message only occurs in the SHE main operating panel with the door closed or the door contact 
switch pressed! 
 

1)   The control panel is completely installed, without the operating voltage applied 

a)  Check all mechanical and electrical components for damage. 
b)  Check the DIP slide switches in the control panel for their correct (required) position. 
c)  Check all screw and plug connections for tightness and/or firm seating. 
d)  Check that all external components are installed. 

Actuators:Is the final module at the last or only actuator inserted? 
Automatic detectors: Is the active end module at the last or only detector inserted? 
Manual detectors: Is the jumper only inserted in the last or only operating panel? 

 

2)   With mains voltage, without accumulator 

Adhere to the relevant regulations!  
a)  Connect the mains cables and reapply the mains voltage. 
b)  The mains LED is ON, the operating LED is OFF, the accumulator LED is ON. The malfunction 

message at the operating panels is ON. 

 

3)   With mains voltage, with accumulator  

a)  Remove the protection film of the lateral adhesive tape for the 1.9 Ah battery, and firmly press the 

two batteries together according to the picture (next page). 

b)  Remove the protection film from one face of the supplied foam rubber. Glue each foam rubber to the 

bottom side of the accumulators. Connect the accumulators to the black accumulator bridge 
according to the wiring diagram, then connect the red and the blue connection cable to the red and 
the black flat plug. Remove the bottom protection film of the foam rubber and insert the batteries in 
the control panel according to figure 1, and firmly press down to the housing bottom! 

c)  Plug the red connection cable to the + and the blue connection to the flat plug of the control panel. 

Note: Check correct polarity! 

d)  The operating LED is ON, the accumulator LED is OFF. The malfunction message at the operating 

panels is OFF. 

 

4)   Ventilation keypad 

Closely observe the actuators during opening and closing. They must not be impaired in any position by 
the building structure. Also the motor connection cables must not be subject to pulling or crushing. 
a)  Briefly actuate the Open button to have the actuators move open up to the final position. With the 

SW2/2 =ON (hold-to-run) setting, the actuators only move as long as the button is pressed. The 
OPEN display (if existing) in the button is ON. 

b)  Briefly actuate the CLOSED button, the actuators close. The Open display is OFF. 
c)  Press both buttons simultaneously while running, this corresponds to stop. The ventilation Open 

display is ON, the actuators stop. 

d)  Briefly press the Closed button again, the actuators fully close, the Open display is OFF. 

 

5)   Break glass unit, primary 

a)  Open the door and press the red Open button. The actuators move open through to the end position. 

The red alarm LED (also in the control panel) is ON, at the same time a permanent acoustic signal 
sounds (door contact pressed!). 

 

For the WSC 204KP, where the break glass unit is located in the door, the break glass unit must be 
exposed before the buttons can be pressed. To expose the break glass unit, the white plastic lever 
arm on the backside of the door must be turned counter clockwise, hereafter the glass can gently be 
pushed upwards and the break glass unit is exposed. When the glass is to be locked again, the lever 
arm is turned clockwise. This is only necessary when the break glass unit in the door is the only 
primary break glass unit and the signal cannot be deactivated from another primary break glass unit. 

b)  While running, press the Closed button at the ventilation button, then press both buttons, the 

actuators must neither close nor stop! 

c)  Press the reset/Closed button in the operating panel. The actuators close through to the end position. 

The ventilation function is released again. The red alarm LED (also in the control panel) and the 
signal generator are OFF. 

6)   Break glass unit, secondary 

a) 

Check as described under 5). „Operation“, „Malfunction“ and the acoustic signal are missing! 

 

Summary of Contents for WSC 204

Page 1: ...04BZ 0102 WSC 204KP 0102 install 1606 UK WindowMaster 2011 2016 WindowMaster is a registered trademark used under licence by WindowMaster Group WSC 204 WSC 204 0102 WSC 204MH 0102 WSC 204KP 0102 WSC 2...

Page 2: ...10 4 6 Back up batteries charge 10 4 7 Operation Setting possibilities 10 5 Installation 11 5 1 Surface mounting 11 5 2 Countersunk mounting 12 5 3 Cable routing 12 5 4 Installation 12 5 5 Installatio...

Page 3: ...ause death severe injury or considerable damage to assets The connection of the control system is reserved for qualified personnel Disconnect all poles of the unit from the supply voltage prior to ope...

Page 4: ...batteries are fully charged 1 9Ah Current load of the actuators battery and 230V operation max 4 8A Current load of the smoke unit batteries surveillance periphery max 0 7A Switch on duration 40 ED Re...

Page 5: ...ights to make changes 2 1 Accessories Alarm and fault module master slave WSA 301 Linking of wind rain signal module WSA 302 Timer ventilation module WSA 303 Gap ventilation module WSA 304B ASV Module...

Page 6: ...6 3 Operating elements and fuse review...

Page 7: ...ators The first 30 min after a SHE trig on WSC 204BZ only when triggered the break glass unit the actuators will be cyclically activated every 2 min in OPEN direction to loosen frost fastened windows...

Page 8: ...on is only displayed in the corresponding smoke control panel and in the break glass unit connected to the master smoke control panel primary break glass unit type WSK 320 Option ASV connection module...

Page 9: ...entilation function is out of operation and the green wind rain LED lights Activated alarm has 1 priority Option Transmission of the wind rain signal module WSA 302 The activated signal of the wind ra...

Page 10: ...ossible Preset To show the activation the LED will flash 10 sec If SW1 1 is once again set on OFF during these 10 sec the prioritised activation is cancelled After a period of 12 month the inspection...

Page 11: ...f Flashes when interrupted Lits when short circuit Check wiring and jumper J1 in the last or only break glass unit Rauchmelder smoke detector yellow Off Flashes when interrupted Lits when short circui...

Page 12: ...E30 See also Cable Length page 12 However this has to be agreed with the Engineer or if necessary with the local fire protection department Do not reduce the cable cross sections specified in the cabl...

Page 13: ...bles cross sections please refer to the following table Maximum actuator current 4 8A Note Be aware of the overall capacity of the smoke control panel Actuating current Sum of all motor currents per g...

Page 14: ...14 7 Cable plan Smoke control panel WSC 204 204MH 204BZ 204KP With back up batteries Mains 230VAC 50 60Hz 150W...

Page 15: ...15 8 Wiring diagram 8 1 Standard wiring diagram...

Page 16: ...16 8 2 Wiring diagram WSC 204KP...

Page 17: ...17 8 3 Various wiring diagrams...

Page 18: ...accumulator LED is OFF The malfunction message at the operating panels is OFF 4 Ventilation keypad Closely observe the actuators during opening and closing They must not be impaired in any position by...

Page 19: ...they will automatically close after 2 minutes e Test the SHE trip and reset closed as described under 5 f Refit the mains fuse g The green mains and operating LED s are ON the yellow accumulator LED i...

Page 20: ...in the smoke panel and the break glass unit Remove all soiling from the units of the smoke and heat extraction system Check fastening and clamping screws for firm seating Carry out a test run of the...

Reviews: