10. Maintenance
The panels of the smoke detection and heat extraction system have to be checked, serviced and, if necessary,
repaired at least once per year by the manufacturer or an authorized system.
If a visual reminder regarding the yearly inspection
is wanted, pls. see section “Commisioning and
troubleshooting” part 9. After a period of 12 month the inspection indication will be activated: the yellow fault
LED in the main break glass unit will flash and the audible fault alarm will sound. The green operating LED will
still flash to show that there is no fault. A reminder will be given as a green and a yellow LED in the smoke
panel and the break glass unit.
Remove all soiling from the units of the smoke and heat extraction system. Check fastening and clamping
screws for firm seating.
Carry out a test run of the entire system (see chapters Start-up and Test Run).
Only have defective units repaired in our factory. Only install original spare parts.
Check the operational condition at regular intervals. We recommend a WindowMaster service contract is taken
out to ensure the right function of the smoke and heat extraction system.
All back up batteries coming with the smoke control panel as standard; have to be subjected to regular checks.
Within the framework of the service, they have to be replaced after the specified maximum 4 year operating
period.
Adhere to the laws governing the disposal of hazardous substances (e.g. batteries).