4.5.  Optional plug-in modules 

 

Module WSA 301 

– alarm and fault module (master/slave) 

 

Module WSA 302 

– linking of wind/rain signal 

 

Module WSA 303 - ventilation time module 

 

Module WSA 304B 

– gab ventilation module (only WSC 204 / WSC 204MH) 

 

Module WSA 306 

– ASV module    

 

4.6.  Back-up batteries charge 

 

Charging voltage: 27.7 -

– 27.8V at 20ºC.  

Charging current: is limited by the safety fuse 0,63A (F3).  
Charging voltage disconnected in the event of a short-circuit .  

 

 
Replace the emergency back-up batteries at least every 4 years!

 

 

4.7.  Operation/ Setting possibilities  

 

Operation / LED diagnose 

Pushing the reset button on the circuit board the SHE activation is reset and the actuators closes. 

 

Setting possibilities via slide switch SW1 

SW 1/1 = ON 

Statutory inspection activated 

SW 1/1 = OFF 

Statutory inspection indication not activated. After activation only a coded deactivation is  

                         possible. (Preset) 

To show the activation the LED will flash 10 sec. If SW1/1 is once again set on OFF during these 10 sec., the 
prioritised activation is cancelled. 

 

After a period of 12 month the inspection indication will be activated: the yellow fault LED in the main break 
glass unit will flash and the audible fault alarm will sound. The green operating LED will still flash to show that 
there is no fault. An alarm signal has first priority. 

 

SW 1/2 = ON 

Forwarding the alarm signal (WSA 301). After 3 min. it will stop.  

SW 1/2 = OFF 

Forwarding the alarm signal (WSA 301) as long as the alarm is trigged. (Preset) 

 

Setting possibilities via slide switch SW2 

SW 2/1 = ON 

 

The SHE alarm trips when malfunction signal from actuator, smoke sensor, break glass 
unit, max. temperature sensor or blown temperature fuse.

 

SW 2/1 = OFF 

No SHE alarm tripped when malfunction signal. Malfunction only shown on the LEDs. 
(Preset) 

 

SW 2/2 = ON 

The actuators 

only

 open for as long as the keypad is pressed (dead man control) 

SW 2/2 = OF 

The actuators will open if the keypad is activated (selfhold). (Preset) 

 

Summary of Contents for WSC 204

Page 1: ...04BZ 0102 WSC 204KP 0102 install 1606 UK WindowMaster 2011 2016 WindowMaster is a registered trademark used under licence by WindowMaster Group WSC 204 WSC 204 0102 WSC 204MH 0102 WSC 204KP 0102 WSC 2...

Page 2: ...10 4 6 Back up batteries charge 10 4 7 Operation Setting possibilities 10 5 Installation 11 5 1 Surface mounting 11 5 2 Countersunk mounting 12 5 3 Cable routing 12 5 4 Installation 12 5 5 Installatio...

Page 3: ...ause death severe injury or considerable damage to assets The connection of the control system is reserved for qualified personnel Disconnect all poles of the unit from the supply voltage prior to ope...

Page 4: ...batteries are fully charged 1 9Ah Current load of the actuators battery and 230V operation max 4 8A Current load of the smoke unit batteries surveillance periphery max 0 7A Switch on duration 40 ED Re...

Page 5: ...ights to make changes 2 1 Accessories Alarm and fault module master slave WSA 301 Linking of wind rain signal module WSA 302 Timer ventilation module WSA 303 Gap ventilation module WSA 304B ASV Module...

Page 6: ...6 3 Operating elements and fuse review...

Page 7: ...ators The first 30 min after a SHE trig on WSC 204BZ only when triggered the break glass unit the actuators will be cyclically activated every 2 min in OPEN direction to loosen frost fastened windows...

Page 8: ...on is only displayed in the corresponding smoke control panel and in the break glass unit connected to the master smoke control panel primary break glass unit type WSK 320 Option ASV connection module...

Page 9: ...entilation function is out of operation and the green wind rain LED lights Activated alarm has 1 priority Option Transmission of the wind rain signal module WSA 302 The activated signal of the wind ra...

Page 10: ...ossible Preset To show the activation the LED will flash 10 sec If SW1 1 is once again set on OFF during these 10 sec the prioritised activation is cancelled After a period of 12 month the inspection...

Page 11: ...f Flashes when interrupted Lits when short circuit Check wiring and jumper J1 in the last or only break glass unit Rauchmelder smoke detector yellow Off Flashes when interrupted Lits when short circui...

Page 12: ...E30 See also Cable Length page 12 However this has to be agreed with the Engineer or if necessary with the local fire protection department Do not reduce the cable cross sections specified in the cabl...

Page 13: ...bles cross sections please refer to the following table Maximum actuator current 4 8A Note Be aware of the overall capacity of the smoke control panel Actuating current Sum of all motor currents per g...

Page 14: ...14 7 Cable plan Smoke control panel WSC 204 204MH 204BZ 204KP With back up batteries Mains 230VAC 50 60Hz 150W...

Page 15: ...15 8 Wiring diagram 8 1 Standard wiring diagram...

Page 16: ...16 8 2 Wiring diagram WSC 204KP...

Page 17: ...17 8 3 Various wiring diagrams...

Page 18: ...accumulator LED is OFF The malfunction message at the operating panels is OFF 4 Ventilation keypad Closely observe the actuators during opening and closing They must not be impaired in any position by...

Page 19: ...they will automatically close after 2 minutes e Test the SHE trip and reset closed as described under 5 f Refit the mains fuse g The green mains and operating LED s are ON the yellow accumulator LED i...

Page 20: ...in the smoke panel and the break glass unit Remove all soiling from the units of the smoke and heat extraction system Check fastening and clamping screws for firm seating Carry out a test run of the...

Reviews: