42
4.
For the Service Technician
Automatic ignition
This adjuster is used to set whether electric ignition is present or not.
Factory setting:
depending on condition upon delivery
Fig. 91
Automatic ignition
Yes
No
Save
Back
Fig. 92
Boiler temperature
for restart
75°C
65
Save
Back
75
Restart temperature
The blower switches off if the boiler temperature is too high. The restart
temperature is the temperature at which the blower switches back on and the
boiler resumes normal heating operation.
Factory setting:
75 °C
Possible settings:
65 °C or 75 °C
Burnout
– automatic detection
Burnout characteristics are determined by MESplus thermal distribution
module WVF+. If only “Solid fuel operation” is set on the WVF+, “Burnout”
with embers maintenance is undertaken. With all other settings on the WVF,
a normal burnout is undertaken.
– normal
A normal burnout is always undertaken, i.e. the wood is burnt as best as
possible until no more remains without embers maintenance.
– Ember quantity
Burnout with embers maintenance is always undertaken, i.e. basic embers
are maintained to make it easier to light up again.
Factory setting:
normal
Fig. 93
Burnout
automatic detection
normal
Ember quantity
Save
Back
4.7.3 Actuator test
The following actuators can be selected with the
arrow
buttons, then confirmed
and started using the
Choose
button. The actuators are switched off again after
1 minute. A self-test is started at the end of an actuator test.
– Induced draught fan
– Primary airflap
– Secondary airflap
– O2 heating
– Automatic ignition
Fig. 94
Induced draught fan
Primary airflap
Secondary airflap
O2 heating
Automatic ignition
Back
4.7.2 Parameters
The following parameters can be selected with the
arrow
buttons, then confirmed using the
Choose
button.
– Automatic ignition
– Restart temperature
– Burnout