11
2.
For the Installer
2.4.2 Taking into the building and installing
The appliance must be taken into the building and installed without subjecting it to significant knocks and jolts,
in order to avoid damaging the combustion chamber and/or the parts slipping. The warranty will be invalidated if
the appliance is damaged due to having been taken into the building and installed incorrectly or if the appliance
malfunctions as a consequence of this.
The LogWIN may only be transported upright and without cladding and it is easiest to transport using a lift truck
or by rolling on pipes. When transporting via stairs and the such like, the boiler must be suitably secured. Also
refer to the technical data in section 4.5 for transport dimensions.
Note!
There is a crane lug on the top of the boiler for transport using hoisting winches. The weight can
be reduced by approx. 120 kg by removing parts which are easy to disassemble (e.g. doors, hook-in
plates, burnthrough plates, heating surface cleaning etc.).
The boiler can be installed directly on a non-flammable surface and does not require special foundations.
2.4.3 Minimum clearances
For maintenance and servicing it is essential to comply with the minimum clearances for the walls, hydraulic
components and connection pipes.
All dimensions in mm:
Recommended minimum room heights: 1850 mm
Attention!
Follow the installation guidelines for boiler rooms!
Fig. 5
LogWIN Klassik exhaust pipe upwards – top view
498
883
1102
654
min. 550
min. 400
min. 700
min. 628
min. 200
min. 485
Fig. 6
LogWIN Klassik with exhaust pipe adapter– top view
498
883
1102
654
min. 550
min. 400
min. 700
min. 628
min. 200
min. 228
min. 485