en
8
Installation and operating instructions • Wilo-Control EC-L • Ed.04/2022-09
•
drain (drain)
•
fill (fill)
Selection is via the menu.
“Drain” operating mode
The reservoir or pump chamber is drained. The connected pumps are activated when the
level rises and switched off when the level falls.
“Fill” operating mode
The reservoir is filled. The connected pumps are activated when the level falls and switched
off when the level rises.
4.4
Technical data
Date of manufacture*
See rating plate
Mains connection
1~220/230 V, 3~380/400 V
Mains frequency
50/60 Hz
Max. current consumption per pump
12 A
Max. rated power per pump
4 kW
Pump activation type
Direct on line
Ambient/operating temperature
-30 … +50 °C
Storage temperature
-30 … +60 °C
Max. relative humidity
90 %, non-condensing
Protection class
IP54
Electrical safety
Pollution degree II
Control voltage
24 V =/~
Housing material
UV-resistant polycarbonate
Details about the Hardware version (HW) and Software version (SW) can be found on the
rating plate!
*The date of manufacture is stated in accordance with ISO 8601: JJJJWww
•
JJJJ = year
•
W = abbreviation for week
•
ww = calendar week
4.5
Inputs and outputs
Inputs
Hardware
version
Number of inputs
EC-L1 ...
EC-L2 ...
EC-L3 ...
Level measurement
Level sensor
all
1
1
1
Float switch
all
2
3
3
Electrode
From HW 2
2
3
−
Dynamic pressure bell
all
1
1
1
High water level
Float switch
all
1
1
1
Electrode
From HW 2
1
1
−
Dry run/low water level
Float switch
all
1
1
1
Electrode
From HW 2
1
1
−
Pump monitoring
Thermal winding monitor (bimetal)
all
1
2
3
Thermal winding monitor (PTC)
all
−
−
−
(Electrode) leakage detection
all
1
2
3
Other inputs
Extern OFF: for remote switch off of all pumps
In “fill” operating mode, dry-running protection is realised via this input.
all
1
1
1