Installation and operating instructions • Wilo-Control EC-L • Ed.04/2022-09
35
Fig. 36:
Menu 5.09
Menu no.
5.09
Software version: All
Description
Sensor measurement range
Value range
0.25 ... 12.5 m
Factory setting
1.0 m
Explanation
Maximum measured values of the sensor
Fig. 37:
Menu 5.39
Menu no.
5.39
Software version: All
Description
Alarm signal with active “Extern OFF” input
Value range
off, on
Factory setting
off
Explanation
The pumps can be switched off using a separate signal trans-
mitter via the “Extern OFF” input. This function overrides all
other switching points and all pumps are switched off.
•
In the “fill” operating mode – select how the alarm signal
occurs in the event of an active input:
“off”: the “Extern OFF” symbol appears on the LCD display
“on”: the “Extern OFF” symbol and the error code “E068”
appear on the LCD display.
•
“Drain” operating mode – factory setting cannot be
changed!
Fig. 38:
Menu 5.40
Menu no.
5.40
Software version: All
Description
Switch “pump kick” function On/Off
Value range
off, on
Factory setting
off
Explanation
To prevent longer standstill times for the connected pumps, a
periodical test run can be performed (pump kick function):
•
off = pump kick deactivated
•
on = pump kick activated
If the pump kick function is activated, the following menu
items can be set:
•
Menu 5.41: Allows “pump kick” when status is Extern OFF
•
Menu 5.42: Pump kick interval
•
Menu 5.43: Pump kick duration
Fig. 39:
Menu 5.41
Menu no.
5.41
Software version: All
Description
Allows “pump kick” when status is Extern OFF
Value range
off, on
Factory setting
on
Explanation
Select whether a pump kick may take place or not if the Extern
OFF input is active:
•
off = pump kick deactivated if Extern OFF is active.
•
on = pump kick activated if Extern OFF is active.