– The display illuminates and the start screen appears.
- The standby symbol appears in the display.
▶
The switchgear is ready for operation. Start the initial configuration or automatic
mode.
Display with level sensor or dynamic pressure bell
5
1
4
3
2
Fig. 29:
Start screen: Level sensor/dynamic
pressure bell
1
Current pump status:
- Number of registered pumps
- Pump activated/deactivated
- Pumps On/Off
2
Set operating mode (e.g. drain)
3
Current water level in m
4
Standby: Switchgear is ready for operation.
5
Field bus active
Display with float switch or electrodes
5
1
2
3
3a 3b 3c 3d 3e
4
Fig. 30:
Start screen: Float switch/electrode
1
Current pump status:
- Number of registered pumps
- Pump activated/deactivated
- Pumps On/Off
2
Set operating mode (e.g. fill)
3
Switching status of the float switch/electrode
•
0 = Float switch open/electrode not immersed
•
1 = Float switch closed/electrode immersed
4
Standby: Switchgear is ready for operation.
5
Field bus active
Designation of the float switch/electrode depending on the operating mode
No.
drain
fill
3a
High water level
High water level
3b
Pump 2 On
Pump 1 and 2 Off
3c
Pump 1 On
Pump 1 On
3d
Pump 1 and 2 Off
Pump 2 On
3e
Dry-running level
Min. level (low water)
8.5
Start initial configuration
Set the following parameters during initial configuration:
•
Enable parameter input.
•
Menu 5: Basic settings
•
Menu 1: Activation/deactivation values
•
Menu 2: Fieldbus connection (if available)
•
Menu 3: Enable pumps.
•
Set motor current monitoring.
•
Check the direction of rotation of the connected pumps.
Observe the following points during the configuration:
•
If there is no input or operation for 6 minutes:
–
the display illumination is switched off.
–
the display returns to the main screen.
–
parameter input is locked.
•
Some settings can only be adjusted when there is no pump in operation.
•
The menu is automatically adapted based on the settings. Example: The Menus 5.41 …
5.43 are only visible when the “pump kick” function (Menu 5.40) is activated.
•
The menu structure is valid for all EC switchgears (e.g. HVAC, Booster, Lift, Fire, etc.).
This may lead to gaps in the menu structure.
8.5.1
Enable parameter input
As standard, the values are only displayed. To change the values, the parameter input in
Menu 7.01 must be enabled: