Installation and operating instructions • Wilo-Control EC-L • Ed.04/2022-09
13.1.4
Connection, thermal motor monit-
oring
x
Fig. 76:
Overview of connections, terminal
layout
Connect the bimetallic strip to the terminal strip for active ex-mode (see Overview of com-
ponents [
14], item 4b).
Use the terminal number shown in the connection overview on
the cover.
The “x” in the symbol states the respective pump.
See also
▶
13.1.5
Dry-running protection connec-
tion
!
Fig. 77:
Overview of connections, terminal
layout
DANGER! Risk of explosion due to incorrect execution! Monitoring of the dry-running
level must be performed with a separate float switch!
Connect the float switch to the terminal strip for active ex-mode (see Overview of compon-
ents [
14], item 4b).
Use the terminal number shown in the connection overview on the
cover.
See also
▶
13.1.6
Switchgear configuration: Switch-
ing on ex-mode
Adapted functions
Ex-mode adapts the following functions:
•
Follow-up times
All follow-up times are ignored and the pumps switched off immediately!
•
Dry-running level (by level sensor or dynamic pressure bell)
The following actions are only possible once the “All pumps off” fill level has been ex-
ceeded:
–
Reactivation of the pumps
–
Resetting the error message
•
Alarm dry-running protection (via float switch)
Alarm manual reset (anti-reactivation lock)!
•
Alarm thermal motor monitoring
Alarm manual reset (anti-reactivation lock)!
Activating ex-mode
1.
Press the operating button for 3 s.
⇒
Menu 1.00 appears.
2.
Turn the operating button until menu 5 appears.
3.
Press the operating button.
⇒
Menu 5.01 appears.
4.
Turn the operating button until menu 5.64 appears.
5.
Press the operating button.
6.
Change the value to “on”: Turn the operating button.
7.
Press the operating button.
▶
Ex-mode switched on.