en
38
Installation and operating instructions • Wilo-Control EC-L • Ed.04/2022-09
Fig. 50:
Menu 5.65
Menu no.
5.65
Software version: All
Description
Automatic resetting of error “Dry run”
Value range
on, off
Factory setting
on
Explanation
If the fill level is over the dry run level again, the error message
“dry run” is automatically reset.
•
on = function activated
•
off = function deactivated
Fig. 51:
Menu 5.66
Menu no.
5.66
Software version: All
Description
Integrated buzzer On/Off
Value range
off, error
Factory setting
off
Explanation
Switching the buzzer on or off:
•
off = buzzer off
•
error = buzzer on
NOTICE! Alarm in the event of interrupted power supply: To
switch off the internal buzzer if there is a built-in re-
chargeable battery, remove the battery!
Fig. 52:
Menu 5.67
Menu no.
5.67
Software version: All
Description
Output (24 V=, max. 4 VA) On/Off for an external signalling unit
Value range
off, error
Factory setting
off
Explanation
Separate output to switch an external alarm signal on or off:
•
off = output deactivated
•
error = output activated
Fig. 53:
Menu 5.68
Menu no.
5.68
Software version: All
Description
Mains connection rotating field monitoring On/Off
Value range
on, off
Factory setting
on
Explanation
Integrated rotating field monitoring for the mains connection.
If no clockwise rotating field is present, an error message oc-
curs.
•
off = rotating field monitoring deactivated
•
on = rotating field monitoring activated
NOTICE! When operating the switchgear via a single-phase
current connection, switch off this function!